6. Description of Parameters
- 190 -
Value
Function
Description
0
No function
Set reserved terminals to 0 to avoid malfunction.
1
Forward run (FWD)
The DI terminals selecting these two functions control forward and
reverse running of the AC drive.
2
Reverser run (REV)
3
Three-wire control
The DI terminal set for this function determines three-wire control
mode of the AC drive.
4
Forward jog (FJOG)
FJOG indicates forward jog running, and RJOG indicates
reverse jog running. Jog frequency, jog acceleration time and jog
deceleration time are described respectively in F8-00, F8-01 and
F8-02.
5
Reverse jog (RJOG)
6
Terminal UP
The terminals selecting these two functions are used for increment
and decrement when frequency reference is input via external DI
terminal, or when frequency source is digital setting.
7
Terminal DOWN
8
Coast to stop
When terminal set for this function becomes on, the drive shuts off
output and the stop process of motor is not controlled by the drive.
It means the same as coast to stop described in F6-10.
9
Fault reset (RESET)
You can perform fault reset via DI terminal set for this function. It
is the same as function of the RESET key on the operation panel.
Remote fault reset is implemented by this function.
10
RUN disabled
When the terminal set for this function becomes on, the AC drive
decelerates to stop and retains all running parameters, such as
PLC, wobble and PID parameters. Once the terminal becomes off,
the AC drive resumes the running status before stop.
11
External fault NO
input
When terminal set for this function becomes on, the drive detects
ERR15 and performs fault protection. For details, see
.
6
6.9 Control Circuit Terminals
This section describes functions of DI, DO, virtual DI, virtual DO, AI and AO terminals.
6.9.1 Function of DI Terminals
Function Code
Parameter Name
Setting Range
Default
F4-00
DI1 function selection
0 to 59
1
F4-01
DI2 function selection
0 to 59
4
F4-02
DI3 function selection
0 to 59
9
F4-03
DI4 function selection
0 to 59
12
F4-04
DI5 function selection
0 to 59
13
F4-05
DI6 function selection
0 to 59
0
F4-06
DI7 function selection
0 to 59
0
F4-07
DI8 function selection
0 to 59
0
F4-08
DI9 function selection
0 to 59
0
F4-09
DI10 function selection
0 to 59
0
These function parameters allocate ten digital terminals with functions. There are five digital
terminals on the control board, DI1 to DI5. There are five additional digital terminals on the
optional I/O extension board, DI6 to DI10.
The functions of digital input terminals are described in the following figure.
Содержание GT600-4T132G
Страница 1: ...GT600 AC Drive...
Страница 5: ......
Страница 86: ...5 Quick Setup 5 1 Get Familiar With Operating Panel 86 5 2 Setup Flowchart 87...
Страница 87: ......
Страница 100: ...5 Quick Setup 98 5...
Страница 280: ...8 Peripherals and Options 278 8...
Страница 306: ...12 303 11...
Страница 362: ......