ULTRAFLOW® 54 DN15-125
42
Kamstrup A/S · Technical description · 5512-2464_D1_GB_09.2021
6.6.2
Recommendations for heat installations
Heat installations
Threaded meter housing with q
p
≤ 2.5 m
3
/h
Threaded meter housing with q
p
≥ 3.5 m
3
/h
and flange meters
(a)
(b)
Figure 17. Acceptable orientation of Kamstrup flow sensors around the pipe axis
for heating installations at horizontal mounting. (a) Threaded meter housings with q
p
≤
2.5 m
3
/h.
(b) Threaded meter housings with q
p
≥
3.5 m
3
/h and flange meters.
'
The orientations
marked with “
!
” are conditionally accepted when the assumptions below are fulfilled.
(1)
District heating/cooling water must be clean and must not contain any kind of dirt. Dirt can otherwise be
deposited on the transducers of the flow sensor, which affects their ability to detect and transmit the ultrasound
signal.
(2)
District heating water must be free of air. Air bubbles will interfere severely with the ultrasound signal.