MULTICAL® 803
Kamstrup A/S · Technical description · 5512-2360_A1_GB_02.2019
35
4
Inputs A and B are currently updated in the display of MULTICAL® 803, i.e. the display of the connected water or
electricity meter will be in accordance with the display of MULTICAL® 803 without delay.
5
The unit of this reading is fixed at kW.
3.4.5
Tariffs >EE<
MULTICAL® 803 has three extra registers TA2, TA3 and TA4, which can accumulate heat energy or cooling energy
(EE=20 accumulates volume) parallel to the main register based on preprogrammed tariff conditions (to be stated in
the order of the calculator). Irrespective of the selected tariff type, the tariff registers are named TA2 TA3 and TA4 in
the display.
As the main register is considered the legal billing register, it is accumulated no matter the selected tariff function.
Tariff conditions TL2, TL3 and TL4 are monitored at every integration. If the tariff conditions are fulfilled, consumed
heat energy is accumulated in either TA2, TA3 or TA parallel to the main register.
Example of power tariff (EE=11)
0
10
20
30
40
50
60
70
0
5
10
15
20
25
30
Po
w
er
[k
W
]
Integrations
Power (P)
TL4
TL3
TL2
Three tariff conditions, TL2, TL3 and TL4, which are always used in the same tariff type, are connected to each tariff
function. Therefore, it is not possible to “mix” two tariff types, except from the PQ tariff (EE=21).
TA2 shows energy consumed…
…above the power limit TL2
IMPORTANT: Out of consideration for backwards compatibility, tariff register TA4 can be deactivated. Thus, the
meter uses TA2 and TA3 only, and the tariff function works as in the previous model, MULTICAL® 801.
TA4 is deactivated by setting the tariff limit TL4 to 0.
TA3
TA4
TA2
M
ai
n r
eg
iste
r