Kamstrup A/S • 5512603_C1_GB_03.2016
MULTICAL® 801
3.2
Mounting of ULTRAFLOW® ≤ DN125
ULTRAFLOW® can be mounted
vertically, horizontally or at an angle.
90°
90°
ULTRAFLOW® may be turned up to
±45° around the pipe axis.
The electronics/plastic box must
be placed on the side (at horizontal
mounting).
Max. 45°
Max. 45°
The ULTRAFLOW® housing must
not be mounted facing upwards or
downwards.
3.2.1
Humidity and condensation
When installed in humid environments ULTRAFLOW® must be turned 45°
around the pipe axis as shown below.
If condensation is likely, e.g. in
cooling systems, an ULTRAFLOW®
which is protected against
condensation must be used.
45°
3.3
Mounting of ULTRAFLOW® 54 ≥ DN150
See installation instructions No. 5512-887.