4  Mounting of flow sensor

Prior to installation of the flow sensor, the 
system should be flushed and protection 
plugs/plastic diaphragms removed from the 
flow sensor.
Correct flow sensor position (inlet or outlet) 
appears from the display of MULTICAL® 302. 
The flow direction is indicated by an arrow on 
the side of the flow sensor.
The flow sensor may be used in both PN16 and 
PN25 installations and is available marked 
either PN16 or PN25 or marked both PN16 and 
PN25, as required.

A

A

SECTION A-A 

SCALE 2 : 1

Tightening by hand

O-ring

Gasket

12 mm

Enclosed couplings, if any, are only intended for PN16. Suitable PN25 couplings must be used in 
PN25 installations.
In connection with G¾x110 mm, it must be checked that 12 mm thread run-out is sufficient. See 
figure below.
Straight inlet: MULTICAL® 302 requires neither straight inlet nor straight outlet to meet the Mea-
suring Instruments Directive (MID) 2004/22/ EF and EN 1434:2007. A straight inlet section is only 
necessary in case of heavy flow disturbances before the meter. It is recommended to follow the 
guidelines of CEN CR 13582.

Recommended flow sensor position

Recommended flow sensor position

Unacceptable position due to risk of air 
build-up

Acceptable position in closed systems

A flow sensor should not be placed 
immediately after a valve, except for block 
valves, which must be fully open when not 
used for blocking

A flow sensor should not be placed close to 
the inlet side of a pump

A flow sensor should not be placed close to 
a two-level double bend.

A

B

C

D

E

F

G

In order to prevent cavitation, the operating pressure at MULTICAL® 302 must be min. 1 bar at q

p

 

and min. 2 bar at q

s

. This applies to temperatures up to approx. 80 °C.

MULTICAL® 302 must not be exposed to pressure lower than the ambient pressure (vacuum).

Содержание MULTICAL 302

Страница 1: ...Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com Installation and User Guide MULTICAL 302...

Страница 2: ...n with minimum vibration and fixed installation with considerable or high vibration level respectively Electromechanical environment E1 housing light industry The meter s signal cables must be drawn w...

Страница 3: ...ting the function 11 8 Communication 11 8 1 Wired M Bus communication 11 8 2 Wireless M Bus communication radio 11 9 Setup Mode 12 9 1 Changing the installation position 13 9 2 Changing the energy uni...

Страница 4: ...One temperature sensor is mounted in the flow sensor from the factory The other sensor ought to be mounted as direct sensor Alternatively both sensors must be mounted in sensor pockets as symmetrical...

Страница 5: ...meter is configured for static info codes Info code Description Response time 0 No irregularities 1 Supply voltage has been interrupted 4 Temperature sensor T2 outside measuring range 32 secs 8 Tempe...

Страница 6: ...ight inlet MULTICAL 302 requires neither straight inlet nor straight outlet to meet the Mea suring Instruments Directive MID 2004 22 EF and EN 1434 2007 A straight inlet section is only necessary in c...

Страница 7: ...may be turned upwards to max 45 and downwards to max 90 compared to the pipe axis 4 5 4 5 9 0 9 0 4 5 4 5 9 0 9 0 Important The meter is most sensitive to air bubbles in the water when the plastic ca...

Страница 8: ...e upper left corner of the meter display an icon indicates if the meter is positioned in the inlet or outlet pipe It is very important to ensure that the meter is correctly positioned as either inlet...

Страница 9: ...broken In case of strong condensation e g cooling applications wall mounting of the calculator is recommended see paragraph 5 2 page 10 8 3 2 4 5 9 8 3 2 4 5 9 In connection with compact mounting the...

Страница 10: ...flow sensor 6 Battery supply MULTICAL 302 is battery supplied with either 1 or 2 A cell batteries Optimal battery lifetime is obtained by keeping the battery temperature below 30 C e g by wall mountin...

Страница 11: ...2 wire cable of 1 5 m The connection is independent of polarity and the M Bus interface is galvanically separated from the rest of the meter M Bus comes with primary secondary and enhanced secondary a...

Страница 12: ...readings of Setup loop are listed below including index numbers Setup loop Loop_3 Index number in display 1 0 Customer number No 1 3 01 2 0 Customer number No 2 3 02 3 0 Date 3 03 4 0 Hour 3 04 5 0 Ta...

Страница 13: ...ave the setting press the button for two seconds until OK appears in the display Outlet If the meter is set to be placed in the outlet the text Outlet is displayed In order to change the setting press...

Страница 14: ...nd conversely the least significant digit disappears if e g you change from kWh with 1 decimal to kWh without decimals See examples below Example 1 GJ with 2 decimals B 2 This is an example of how the...

Страница 15: ...or registers the amount of district heating water flowing through the heating system in m3 cubic metres The temperature sensors placed in inlet and outlet pipes register the cooling i e the difference...

Страница 16: ...Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com User Guide MULTICAL 302 Kamstrup A S 55121351_D2_GB_04 2015...

Отзывы: