background image

25

Kamstrup A/S • 55122714_A2_GB_04_2021

flowIQ® Gateway

7.1.1.2 

"SETUP loop"

Please note that it is only possible to configure the gateway 50 times via "SETUP loop". 
After 50 times, the gateway is locked against further configuration and a total reset is 
required. 

"SETUP loop" is intended for the technician. In this loop, the technician can configure the gateway 
via the front keys. It is used for further configuration than done from the factory. 
The loop is accessible in transport mode or until the configuration is ended by activating 
“EndSetup” or letting water flow through the connected flowIQ® 2200/3200 meter. 
You can navigate from "USER loop" to "SETUP loop" by keeping the primary key activated for 5 
seconds until the text "1-USER" appears in the display. Use the arrow keys to navigate to "3-SETUP" 
and press the primary key once to open "SETUP loop" in flowIQ® Gateway.  
You can leave "SETUP loop" in the following ways: 
•  Keep the primary key activated and navigate to the gateway's other loops
•  After 4 minutes without activation of the key, the gateway will time out and return to the first 

reading in "USER loop"

•  Navigate to the menu item “EndSetup” and keep the primary key activated for 5 seconds until 

the display shows “OK”

Navigating and changing parameters in "SETUP loop" 

You can change the parameters of "SETUP loop" as shown in the following example. If the 
parameter you wish to change is not part of the "SETUP loop", you must use METERTOOL HCW with 
an optical read-out head for configuration. 
This example changes the preset values for the inputs In-A1 and In-B1. Navigation of the menu, 
and changing of the preset values, is similar when configuring other parameters. Navigate using 
the index menu listed in "SETUP loop" table below.

1. Enter "SETUP loop". 

Hold down the primary key and release it at “1-USER”.

2. Go to "3-SETUP" using the arrow keys. 

Enter by pressing the primary key.

3. Go to index “3-016” for input In-A1 or index “3-017” for input 

In-B1 by pressing the arrow keys.
Enter the setup by pressing the primary key.

4. Use the primary key to increment the number and the arrow 

keys to navigate.

5. Save your settings by holding down the primary key until 

"OK" appears in the bottom left corner.

......OK

6. Return to "USER loop" by holding down the primary key and 

press once to enter "USER loop".

Содержание flowIQ

Страница 1: ...Installation and operation guide flowIQ Gateway Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 89 93 10 00 info kamstrup dk kamstrup com...

Страница 2: ...ark of Kamstrup to any other party This disclaimer includes but is not limited to implied warranties of merchantability fitness for any particular purpose and non infringement Information in this docu...

Страница 3: ...import in READy Manager 13 5 1 2 Manual import in READy Manager 13 5 1 3 Import in a third party MDM system 13 6 Field deployment installation 14 6 1 Installation 14 6 1 1 Wall installation 14 6 2 Con...

Страница 4: ...y and meter exchanges in READy Manager 31 8 3 1 flowIQ Gateway exchange 31 8 3 2 flowIQ 2200 3200 meter exchange connected to flowIQ Gateway 31 8 4 Kamstrup support 31 9 Disposal 32 9 1 Disposal by Ka...

Страница 5: ...bove 100 C or incinerate the battery Keep away from children By connecting to 230 V supply there is a risk of electric shock Use only approved accessories with this device Unapproved modifications or...

Страница 6: ...lation point in READy Manager only the flow Gateway serial number will be availbale in READy Manager If used with a radio module with internal antenna it is recommended that flowIQ Gateway is mounted...

Страница 7: ...ctions ormisuse ofthe product flowIQ Gateway is an accessory gateway that syncs shows and forwards meter data The connected flowIQ 2200 3200 meter is the solution s legally approved entity MID for bil...

Страница 8: ...module and lifetime depends on the chosen communication modules and datagrams Mains supply 230 VAC 15 30 50 60 Hz 24 VAC 50 50 60 Hz 24 VDC 75 25 24 VDC for High Power SMPS only Power consumption 1 w...

Страница 9: ...on interface 3 6 Input flowIQ 2200 3200 meter Proprietary Kamstrup communication Cable ordered separately 1 5 m 5000491 7 5 m can be shortened 5000493 Temperature sensors 3 x Pt500 3 7 Connections and...

Страница 10: ...ts kamstrup com for further information about data content 3 7 1 3 Supported info codes from flowIQ 2200 3200 meters The connected flowIQ 2200 3200 meters can forward the following alarms info codes t...

Страница 11: ...In A In B HC 003 11 Data Pulse outputs Out C Out D HC 003 20 Wired M Bus inputs In A In B HC 003 21 Wired M Bus outputs Out C Out D HC 003 32 linkIQ wM Bus inputs In A In B EU HC 003 33 linkIQ wM Bus...

Страница 12: ...00 All Pt500 2 wired sensors can be used If a set of two or more sensors are bought from Kamstrup the sensor set can be split to use one sensor per flowIQ Gateway 4 3 Deployment summary 1 Before field...

Страница 13: ...ilbale in READy Manager If using Kamstrup s MDM system READy Manager flowIQ Gateway is automatically imported into READy Manager if you are logged in with your My Kamstrup account and the Import new d...

Страница 14: ...t least 15 cm from pipes and conduits and several centimetres below the ceiling If used with a radio module mount flowIQ Gateway at least 1 5 m away from any large metal objects e g refrigerators HVAC...

Страница 15: ...below Description Schematic Overview The flowIQ 2200 3200 meter cable is connected in the following way Black minus input 11 Red plus input 9 Green V1 input 10 The 3 Pt500 temperature sensors are conn...

Страница 16: ...t the modules as shown The communication modules are programmed with a data package at the factory and will send data according to the chosen package 6 3 1 Antenna mounting All radio based modules mus...

Страница 17: ...t500 temperature sensors Up to 4 x pulse meters Up to 2 x analog input 4 20 mA devices e g pressure sensors 6 4 1 Connecting Pt500 temperature sensors Up to 3 x Pt500 temperature sensors can be connec...

Страница 18: ...ule Upon delivery the configurations of pulse inputs A and B can be changed with METERTOOL HCW The preset value of In A1 and In B1 can be set via the front keys see section 7 Field deployment Configur...

Страница 19: ...tion class II and are connected via a two wire cable without earth through the big cable bush at the bottom of the connection base Use connecting cable with an outer diameter of 5 8 mm and ensure corr...

Страница 20: ...th a 24 VAC VDC or 230 VAC power supply 230 VAC 24 VAC 2 Use a power cable with a diameter of 5 8 mm d 5 8 mm 3 Connect the power cable to the terminals on the right side of flowIQ Gateway seen from t...

Страница 21: ...e device is in transport mode In transport mode all wireless communication is deactivated Wired communication modules respond on request Transport mode can be initiated by disassembling the top and bo...

Страница 22: ...user display loop by pressing the right or left arrow buttons 3 Check the readings Up to 20 seconds can pass before the display is updated with the readings from the flowIQ 2200 3200 meter t1 XX XX t2...

Страница 23: ...ressing the primary key once f fl lo ow wI IQ Q G Ga at te ew wa ay y D Di is sp pl la ay y l lo oo op p Press M Ma ai in n l lo oo op p S Su ub b l lo oo op p L Lo oo op p s se el le ec ct t Press Pr...

Страница 24: ...onthly logger Monthly logger data 5 Input B1 Meter no of input B1 L imp of input B1 Date for yearly logger Yearly logger data Date for monthly logger Monthly logger data 6 Input A2 Meter no of input A...

Страница 25: ...gateway will time out and return to the first reading in USER loop Navigate to the menu item EndSetup and keep the primary key activated for 5 seconds until the display shows OK Navigating and changin...

Страница 26: ...or OFF 3 015 16 0 Input A1 preset register 3 016 17 0 Input B1 preset register 3 017 18 0 Meter number of input A1 3 018 19 0 Meter number of input B1 3 019 24 0 EndSetup 3 024 The clock can under ins...

Страница 27: ...The gateways radio wireless communication is automatically turned on when the gateway leaves the transport mode The radio on off function in the SETUP loop index 3 015 is primarily used for switching...

Страница 28: ...code defines the resolution by which the 24 hours are divided either 48 intervals of half an hour 24 intervals of one hour or 12 intervals of two hours If the gateway registers minimum one pulse durin...

Страница 29: ...evices The synchronization between the flowIQ 2200 3200 meter and flowIQ Gateway is done every 20 seconds 8 2 Alarms and info codes flowIQ Gateway constantly monitors a number of important functions I...

Страница 30: ...In A2 Leakage in the system 1 day flowIQ Gateway 8 In A1 Leakage in the system 1 day 9 In A1 A2 External alarm 5 sec 7 In B2 Leakage in the system 1 day 8 In B1 Leakage in the system 1 day 9 In B1 B2...

Страница 31: ...commended that you perform a Meter exchange in READy App if using Kamstrup s READy MDM solution 8 3 2 flowIQ 2200 3200 meter exchange connected to flowIQ Gateway If a meter exchange is required it is...

Страница 32: ...to previous agreement The disposal is free of charge to the customer except for the cost of transportation to Kamstrup A S 9 2 The customer sends for disposal flowIQ Gateway must not be disassembled...

Страница 33: ...y laminate components soldered on PCB scrap for metal recovery LC display Glass and liquid crystals Approved processing of LC displays Top cover PC 10 GF Plastic recycling or combustion PCB case and c...

Страница 34: ...dule slot 1 has a Modbus output with 2 pulse inputs In A1 and In B1 Module slot 2 has an M Bus module with 2 pulse inputs In A2 and In B2 Only V1 data is available on pulse input For further informati...

Страница 35: ...ample 4 Primary connection terminals Module slot 1 Module slot 2 1 x flowIQ 2200 3200 meter serial V1 connection HC 003 67 1 x Modbus RTU 2 pulse inputs In A In B HC 003 11 1 x Data Pulse 2 pulse outp...

Страница 36: ...Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com Kamstrup 55122714_A2_GB...

Отзывы: