Installation 

PULSE DIVIDER 

for ULTRAFLOW

®

 

English 

 

Kamstrup A/S 
Industrivej  28,  Stilling,  DK-8660  Skanderborg 
TEL:  +45  89  93  10  00  ·  FAX:  +45  89  93  10  01 

[email protected]

 · 

www.kamstrup.com

 

Содержание 66-99-607

Страница 1: ...Installation PULSE DIVIDER for ULTRAFLOW English Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg TEL 45 89 93 10 00 FAX 45 89 93 10 01 info kamstrup com www kamstrup com...

Страница 2: ...nstallation guide no 5511 704 3 Electrical connection PULSE DIVIDER 3 Pulse output Passive STANDARD 66 99 607 4 Pulse output Active re configured 66 99 606 4 Re configuration 5 Tabels for PULSE DIVIDE...

Страница 3: ...supply 9A 9 Yellow signal 10A 10 10A 10 The use of long signal cables requires careful handling in connection with installation Signal cables must be installed at least 25 cm from other cables due to...

Страница 4: ...connection Voltage range 3 6 VDC Max leak current 1 A Min Rload 30 k Max Rload 1 M 3 wire connection Supply 9A 3 10 VDC lmax 0 2 mA Flow chart PULSE DIVIDER Pulse output Active re configured 66 99 606...

Страница 5: ...ER re configured to an active output Re configuration Re configuration of the PULSE DIVIDER from passive to active pulse output is made by adding 2 pcs 820 1 8 W resistances to the connection print Pl...

Страница 6: ...0 15 25 375 15 10 10 100 15 10 25 250 15 10 100 1000 15 10 250 2500 25 10 10 100 25 10 25 250 25 10 100 1000 25 10 250 2500 ULTRAFLOW Pulse Divider qp m3 h Meter factor Pulses l Meter factor l Pulse D...

Страница 7: ...00 40 600 0 25 100 25 100 25 1000 0 25 100 25 100 25 Table on the use together with Kamstrup EVL U L T R A F L O W qp m3 h Meter factor pulses l PULSEDIVIDER pulseduration Meter factor l pulse and 11...

Страница 8: ......