Wall HK

► 

Assembly, installation and operating instructions

Keep these instructions in a safe place for future use!

Issue04/21EN
SAP No.1428258

Содержание Wall HK

Страница 1: ...Wall HK Assembly installation and operating instructions Keep these instructions in a safe place for future use Issue04 21EN SAP No 1428258...

Страница 2: ......

Страница 3: ...Construction and function 13 5 1 Overview 13 5 2 Brief description 13 6 Installation and wiring 14 6 1 Definition of the connection side 14 6 2 Requirements governing the installation site 14 6 3 Min...

Страница 4: ...1 Securing against reconnection 39 9 2 Maintenance Schedule 39 9 3 Maintenance work 40 9 3 1 Replacing the filter 40 9 3 2 Visual checks 40 9 3 3 Cleaning the condensate tray 40 9 3 4 Clean the inside...

Страница 5: ...apply as do general safety provisions governing the use of the equipment Illustrations in this guide are intended to provide a basic understanding and may differ from the actual model Ongoing tests an...

Страница 6: ...nd proper use Intended use of the unit also includes adherence to these instructions Any use beyond or other than the stated intended use is considered as misuse Any change to the unit or use of non o...

Страница 7: ...of the medium used to protect the equipment The following values provide further guidance The water used should be free of contamination such as suspended substances and reactive substances Water qua...

Страница 8: ...rate the unit above electrical equipment such as switch cabinets computers or other electrical units or contacts that are not drip proof IMPORTANT NOTE Energy losses due to misuse Operating the unit w...

Страница 9: ...owing gained from specialist vocational training Safety and accident prevention regulations Guidelines and recognised technical regulations e g National Electric Code NEC and Canadian Electric Code CE...

Страница 10: ...te IMPORTANT NOTE 2 people are needed to transport the unit Wear personal protective clothing when transporting the unit Only lift the unit on both sides and not by the pipes valves IMPORTANT NOTE Mat...

Страница 11: ...ions and shocks IMPORTANT NOTE Under certain circumstances packages can carry storage instructions that exceed the requirements listed here Comply with these instructions accordingly 3 4 Packaging Han...

Страница 12: ...Sound power level dB A 20 47 21 50 24 52 25 53 Unit Wall HK Model 1 2 3 4 Width of basic unit inch 32 09 43 31 62 99 74 8 Width of casing inch 37 99 49 21 68 9 80 71 Weight of basic unit pound 33 07 4...

Страница 13: ...7 Filter fleece 8 Heat exchanger 5 2 Brief description Wall HK are decentralised units for heating cooling and filtering air for use in hotels offices and business premises among others Secondary air...

Страница 14: ...and operating instructions 14 6 Installation and wiring 6 1 Definition of the connection side Example of 2 pipe connection on left Example of 2 pipe connection on right Example of 4 pipe opposite end...

Страница 15: ...met Make sure that the unit is securely suspended standing Ensure that the airflow can circulate freely Provide adequate space for appropriately sized flow and return water connections on site Connec...

Страница 16: ...pletely unobstructed to guarantee the free circulation of air There needs to be a 50 mm freely accessible clearance above the casing to remove the casing Example of basic unit wall standing without ca...

Страница 17: ...structed to guarantee the free circulation of air There needs to be a 50 mm freely accessible clearance above the casing to remove the casing Example of basic unit wall standing without casing Example...

Страница 18: ...have sharp edges Wear suitable protective gloves IMPORTANT NOTE Horizontal installation of units When installing the units ensure that they are completely horizontal to ensure proper operation IMPORTA...

Страница 19: ...C 35 230 109 15 0 8 5 0 21 374 140 A 225 124 60 64 15 21 124 B 142 142 D 124 C 35 230 105 15 0 8 5 0 21 370 140 Front view Top view Keyhole detail Side view Fig 4 321 Dimensions of basic unit and moun...

Страница 20: ...3 20 9 43 3 32 1 33 5 32 1 63 51 8 53 2 51 8 74 8 63 6 65 63 6 Tab 5 Table of dimensions inch Note the Venkon minimum clearances when installing the basic units Highlight the dimensions and clearance...

Страница 21: ...ng instructions 21 6 4 2 Installation of casing Isometric view Front view Top view Isometric view Front view Wall hanging casing In wall casing Fig 6 Dimensions of casing mm Model A mm 1 965 2 1250 3...

Страница 22: ...n and operating instructions 22 Isometric view Front view Top view Isometric view Front view Wall hanging casing In wall casing Fig 7 Dimensions of casing inch Model A mm 1 38 2 49 2 3 68 9 4 80 7 Tab...

Страница 23: ...Dismantle the casing wall mounted Unscrew the screws on the left and right side of the air outlet Remove the casing wall mounted First remove the casing upwards and then away from the basic unit Fixi...

Страница 24: ...the casing upwards where it was previously screwed in place to loosen it from its fixing Remove the casing Adjust the casing recessed in the wall to the depth of the wall recess The retaining rails fo...

Страница 25: ...ection can be changed by altering the discharge adjustment plate A Front air discharge direction B Top air discharge direction Fig 10 Discharge adjustment plate secured by a metal screw Note When alte...

Страница 26: ...ent plate Loosen the flat headed screws on the left and right to al ter the discharge adjustment plate the example shows alteration from front air outlet to top air outlet Loosen the middle metal scre...

Страница 27: ...hout bends and narrow sections with a gradient to the in situ waste water pipe Allow adequate space for the air flow air inlet and outlet During cooling operation also observe the following points Pro...

Страница 28: ...is a danger of scalding from escaping heating me dium With cooling units there is a danger to the user from cold temperatures and a danger to the environment from the use of glycol Take appropriate sa...

Страница 29: ...g flow with 2 pipe heating or cooling 4 Heating return 5 Heating flow 6 Air vent Dimensions in brackets basic unit front discharge Side view heating or cooling 2 pipe connection on left Side view heat...

Страница 30: ...ervice hatch dimensions for maintenance and inspection of basic unit with casing by others Fig 14 Dimensions of service hatch mm Model Ceiling opening dimension A 15 mm 1 925 2 1225 3 1675 4 2025 Fig...

Страница 31: ...n and operating instructions 31 6 5 2 Insulating the pipework Slide impermeable insulation by others along the pipe through the wall opening as far as the straight valve so that the insulation only en...

Страница 32: ...r wall connection pipework simplified view mm Fig 16 Space for water connection pipework mm Front view 2 pipe connection on left Front view 2 pipe connection on right Front view 4 pipe opposite end co...

Страница 33: ...work simplified view inch Fig 17 Space for water connection pipework inch Front view 2 pipe connection on left Front view 2 pipe connection on right Front view 4 pipe opposite end connections Drilling...

Страница 34: ...all applicable regulations such as the use of a ball trap when connecting the condensation line to the sewer system Protect the trap from drying out The suc tion effect of the fan on the condensation...

Страница 35: ...of the basic unit All models require a power supply 24 V DC and can be controlled via a control input 0 10 V DC Select the internal resistance of the control input for the respective model according t...

Страница 36: ...g J Y ST Y 0 8 mm laid separately from power lines W1 power supply control signal for fan and actuator 3 Building Automa on BMS including central power supply 24VDC 0 10V GND 4 5 DO GND control signal...

Страница 37: ...s connected in accordance with the electric wiring diagrams Check all external electrical connections and terminal connections are fixed in place and tighten if necessary Water side checks Check wheth...

Страница 38: ...an alarm signal Check whether the unit is connected leak free to the on site condensation connection Check whether the waste water lines are clean and have a sufficient gradient Check whether the cond...

Страница 39: ...he proper and trouble free operation of the equipment If there are signs of increased wear during regular checks shorten the required maintenance intervals to the actual wear and teat Contact the manu...

Страница 40: ...e sharp edges Wear suitable protective gloves Pull the filter from the Velcro strip remove any dirt or change the filter if necessary 9 3 2 Visual checks Check heat exchanger for dirt and carefully va...

Страница 41: ...screw the 4 fixing screws Remove the condensate tray from the basic unit Clean the condensate tray 9 3 4 Clean the inside of the unit Check all elements that come into contact with air internal surfac...

Страница 42: ...ne Check flow and return and tighten if necessary Water outlet Condensate drain outlets blocked Clean condensate outlets and check for ad equate gradient Chilled water line incorrectly insulated Check...

Страница 43: ...ing clips are removed during cleaning Fan dirty Clean dirt from fan Heat exchanger dirty Clean dirt from Heat exchanger 10 2 Start up after rectification of fault After correction of the fault carry o...

Страница 44: ...Wall HK Assembly installation and operating instructions 44 11 Certificates...

Страница 45: ...Table Tab 1 Limits of operation 7 Tab 2 Operating voltage 7 Tab 3 Water quality 7 Tab 4 Table of dimensions mm 19 Tab 5 Table of dimensions inch 20 Tab 6 Dimensions of casing mm 21 Tab 7 Dimensions o...

Страница 46: ......

Страница 47: ......

Страница 48: ...Country Contact Canada Kampmann Heating Cooling Ventilation Ltd 600 890 West Pender Street Vancouver BC V6C 1J9 T 1 604 3621080 F 1 604 6871327 E info kampmann ca W Kampmann ca 04 21 ENSAP Nr 1428258...