Tandem door air curtains
Door air curtains with patented Tandem technology
Assembly, installation and operating instructions
26
6.4.2 Connection to the pipe network
The flow and return connections are located as standard at the side of the casing on the left side of the unit, as seen from the
air intake. The heat exchanger connection is 3/4".
Proceed as follows when connecting up the unit's hydraulic pipework:
Shut off the supply line from the heating medium.
Connect up the pipework.
Remove protective caps from the flow and return.
Seal and screw in connections, holding the nut to prevent it from shearing off and twisting.
Important! Use an appropriate tool (e.g. wrench AF 32) to secure the connecting nut and prevent it from shear-
ing and twisting! Ensure that the connections experience no mechanical tension when fitted!
6.4.3 Fitting the thermoelectric shut-off valve and outlet temperature limit valve
5
4
3
1
2
6
Fig. 16: Thermoelectric shut-off valve and outlet temperature limit valve, shown on Tandem 300
1
Flow ¾“
2
Return ¾“
3
Outlet temperature limit valve, type 103968; installation in the
flow
4
Thermoelectric shut-off valve, type 100912
5
Opening for remote sensor for outlet temperature limit valve (ac-
cessory)
6
Opening for connecting cable for thermoelectric shut-off valve
(accessory) and electrical wiring