![Kampmann Katherm HK Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/kampmann/katherm-hk/katherm-hk_assembly-installation-and-operating-instructions_3508573044.webp)
Katherm HK
Assembly, installation and operating instructions
44
7.3
Electromechanical connection, 230 V (*00)
230 V circuit description (*00)
All trench heaters need a 230 V / 50 Hz power supply.
Factory-fitted actuators are wired to the terminals. The appropriate terminals are available for valve actuators.
The fan speed of the EC fans used can be continuously variably controlled by a 0-10 V DC signal. The internal motor elec-
tronics detects any possible motor malfunction and automatically switches off the fan.
2
1
3
1
2
3
Junction box for HK 320/130, 245/160, 360/210
Junction box for HK 290/160
Fig. 10: Electromechanical junction box (*00)
1
Power supply
2
Valve actuators
3
Speed signal
Control via 0 – 10 V DC
control signal
Function
0 V
Off
1.5 V – 10 V
0 – 100%