9 Technical data

9.1 Technical specifications

Combi Port E D-UFH

Value

Medium

Heating water according to VDI 2035

Operating temperature

5-85 °C (90 °C temporary)

Max. operating pressure

10 bar, heating
10 bar, domestic water

Max. primary differential
pressure

1.2 bar ( 4.5 bar with differential pressure
regulator)

Combi Port E D-X

Value

Medium

Heating water according to VDI 2035

Operating temperature

5-85 °C (90 °C temporary)

Max. operating pressure

10 bar, primary heating
3 bar, secondary heating
10 bar, domestic water

Max. primary differential
pressure

1.2 bar ( 4.5 bar with differential pressure
regulator)

Combi Port E controller

Value

Operating voltage

230 V AC, 50 Hz

Power consumption

1 W

Safety

T 2 A, 250 V

Ambient temperature

-10 °C … +40 °C (max.)

Protection code

IP 42

Pump/relay output

230 V AC, 200 W (max.)

Valve output

See table below

Material

Value

Fittings, sanitary

CW617N

Fittings, heating

CW617N, CW614N

Seals

According to DVGW KTW, W270

Turbine

POM with KTW approval

Insulation

EPP

Plate heat exchanger

1.4404

Soldering

Copper, vacinox

Pipes

1.4404

Uponor Vario S manifold

Value

Medium

Heating water according to VDI 2035

Operating temperature

5-60 °C

Operating pressure

10 bar

Grundfos pump UPM3

Value

Medium

Heating water according to VDI 2035

Operating temperature

5-95 °C

Operating pressure

10 bar

Connection

DN 15 (G1“)

Power connection

230 V, 50/60 Hz

Electrical current, max.

0.44 A

9.2 Electrical connection controller

Electrical net connection, 230 V AC

Contacts

Description

Marking

L

(X1)

Phase

Black/Brown

Net

N

Neutral

Blue

Net

PE

Protective
conductor

Green/Yellow

Net

Relay outputs, max 230 V AC, 200 W

Contacts

Description

Marking

L2

(X3)

Phase

Black/Brown

Circulation pump

N

Neutral

Blue

Circulation pump

PE

Protective
conductor

Green/Yellow

Circulation pump

L3

(X4)

Phase

Black/Brown

Heating pump 1

N

Neutral

Blue

Heating pump 1

PE

Protective
conductor

Green/Yellow

Heating pump 1

DC valve outputs for motor valves

Note

Only suitable for connecting motor valves.

Contacts

Description

Marking

V1

(X27) Control signal

Red

Valve cold water

Control signal

Black

Valve cold water

V2

(X28) Control signal

Red

Valve heating 1

Control signal

Black

Valve heating 1

Temperature sensor input

Note

Room thermostat and/or outdoor temperature sensor
must be connected to a 2-pin connector on site.

Contacts

Description

Marking

Earthing on site for T1-T10

T1

(X15) Measurement signal

Domestic hot water

T2

(X16) Measurement signal

Heating supply (primary)

T3

(X17) Measurement signal

Heating supply (secondary)

T4

(X18) Measurement signal

Heating return (secondary)

T7

(X22) Measurement signal

Cold water

T8

(X21) Measurement signal

Heating return (primary)

T9

(X23) Measurement signal

Room thermostat

T10

(X24) Measurement signal

Outdoor temperature
sensor

22 

 |  

Combi Port E D

  |  

Installation and operation manual

Содержание uponor Combi Port E D

Страница 1: ...Combi Port E D EN Installation and operation manual CD0000XXX CD0000390...

Страница 2: ...ponents devices 14 5 5 Filling flushing and venting 14 6 Operation 15 6 1 Hydraulic balancing on the manifold 15 6 2 Constant pressure pump control 15 6 3 Combi Port E mobile application 16 6 4 Commis...

Страница 3: ...products approved or specified by Uponor is not connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and does not show evidence of tamperi...

Страница 4: ...ble vapours or gases Uponor cannot accept any responsibility for damage or breakdown that can result from ignoring these instructions 2 2 Standards and regulations Note The installation must be carrie...

Страница 5: ...for details of where and how they can take this item for environmentally safe recycling Business users should contact their supplier and check the terms and conditions of the purchase contract This pr...

Страница 6: ...nsists of many individual components which are described below The unit can also be equipped with accessories like heat meters and components from the Uponor room temperature control system both wired...

Страница 7: ...e following accessories are optional Their use completes the product portfolio The application is described in more detail in the following chapters Port Base and pipe connection set CD0000367 Port Ba...

Страница 8: ...m control functions This list shows available functions for the different systems Basic Functions Wave Pulse Base Pulse Base PRO Autobalancing Cooling function Modularity Installation and configuratio...

Страница 9: ...port E D UFH unless nothing else is mentioned The insulation mounted in the unit is removed in the illustrations only to show all components and increase the understanding The installation of Combi Po...

Страница 10: ...escription A Flat gasket 1 Place the flat seals on to the ball valves screw connection 2 Tighten the swivel nuts Connect the primary supply pipes Note Install the pipes in accordance with planning doc...

Страница 11: ...emperature control Note Visit the Uponor download centre for more information regarding the installation and configuration of Uponor Smatrix and Uponor Base flexiboard 4 4 Heat interface unit with Por...

Страница 12: ...sired fittings 2 Connect the underfloor heating pipes to the underfloor heating manifold by using desired fittings Connect the compression fittings SI0000324 1 2 1 Cut the pipe in required length 2 Co...

Страница 13: ...re set pressure is defined based on the calculated static height from the expansion vessel to the highest point in the heating system DI0000023 The pressure in the vessel is pre set to1 0 bar which no...

Страница 14: ...is installed The room temperature signal can also be activated via the individual room control Uponor Smatrix or Uponor Base flexiboard 5 5 Filling flushing and venting Note Switch off the pump befor...

Страница 15: ...gulation valve according to the design calculation 5 Consider the planning documentation 6 2 Constant pressure pump control Note Please read the installation manual from the pump manufacturer CD000039...

Страница 16: ...pp Likewise all settings for domestic water and heating are made via the app Combi Port E app PDF SI0000301 1 Download the Combi Port E app It is available both for iOS and Android mobile devices 2 Sc...

Страница 17: ...ing mode Automatic reconnect Connect when the application returns to the foreground Polling interval Interval in seconds in which displayed values are updated Increase value to consume less battery ch...

Страница 18: ...r OFF Room controller POSSIBLE SETTINGS Operating mode Control mode Time program Heating curve optional ECO mode heating DISPLAYED VALUES Supply secondary Return secondary Outdoor temperature optional...

Страница 19: ...ovided via the central house connection and distribution line The heat interface unit is equipped with a central shut off ball valve for cold water F As an option there is a shut off ball valve for in...

Страница 20: ...display Hotwater Check the controller setting Check setpoints via the App in the display Hot water Waiting time for hot water is too long Check the pump setting in the central heating system Pump set...

Страница 21: ...al heating circuit pump not working Check that the central heating circuit pump is working and correctly set Central strainer is dirty Clean the central strainer Heating system is not working correctl...

Страница 22: ...ure 10 bar Connection DN 15 G1 Power connection 230 V 50 60 Hz Electrical current max 0 44 A 9 2 Electrical connection controller Electrical net connection 230 V AC Contacts Description Marking L X1 P...

Страница 23: ...RS485 interface 4 pin terminal X14 For terminal output or Modbus RTU communication Modbus RTU For data output and possibility to change setting values For communication a Modbus RTU master program dow...

Страница 24: ...2 BN BU M 3 BN BU M 4 BN BU M 5 BN BU M 6 BN BU 12 L L PUMP L N BOILER 24 V L N Power GPI a b a b OK 2 1 T 165 T 163 T 169 T 168 OK T 166 T10 T10 D X7 X3 P J G E N M M G D H I B E N C M N A A M L D F...

Страница 25: ...pply secondary X Heating return secondary Y Domestic hot water to apartment DHW Z Cold water from riser CW AA Circulation optional AB Uponor Smatrix Wave Pulse room controller AC Zone valve for limiti...

Страница 26: ...single room thermostat V W X Y Z AA T10 T10 D X7 X3 P J G E N M M G D H I B E N C M N A A M L D F G T O R T3 X4 M T2 V2 T4 T8 X21 K B V1 Q M T8 X21 K T1 U S WD0000035 26 Combi Port E D Installation a...

Страница 27: ...Contact Description Colour cable tie X21 Heating return primary Blue X22 Cold water from riser CW Green X25 optional X26 optional Temperature sensors Contact Description Colour cable tie T1 Domestic h...

Страница 28: ...E D UFH Combi Port E D X 24 plates Pressure losses Heating side primary DI0000027 0 80 0 70 0 60 0 50 0 40 0 30 0 20 0 10 0 00 100 200 300 400 500 600 700 800 900 1000 1100 1200 A B C Item Description...

Страница 29: ...C 85 C Item Description A Primary heating demand in litres hour l h B Primary heating supply temperatures C Tapping capacity in litres minute l min D Max range Tapping capacity 35 K 10 45 C DI0000030...

Страница 30: ...ting supply temperatures C Tapping capacity in litres minute l min D Max range Tapping capacity 45 K 10 55 C DI0000034 40 35 30 25 20 15 10 5 0 2 4 6 8 10 12 14 16 18 20 22 60 C 65 C 70 C 75 C 80 C 85...

Страница 31: ...nd other internal external fixtures must be included Domestic hot water side secondary DI0000038 1 00 0 40 0 50 0 60 0 70 0 80 0 90 0 30 0 20 0 10 0 00 2 0 4 0 6 0 8 0 10 0 A B 12 0 14 0 16 0 18 0 20...

Страница 32: ...ting supply temperatures C Tapping capacity in litres minute l min D Max range Tapping capacity 40 K 10 50 C DI0000042 40 35 30 25 20 15 10 5 0 18 2 4 6 8 10 12 14 16 20 22 24 A B 55 C 60 C 65 C 70 C...

Страница 33: ...70 C 65 C 75 C 85 C Item Description A Primary heating demand in litres hour l h B Primary heating supply temperatures C Tapping capacity in litres minute l min D Max range Tapping capacity 50 K 10 6...

Страница 34: ...cribes the residual pressure Heating heat exchanger values Primary heating supply 70 C Primary KW Supply C Return C T l h 1 0 70 0 41 0 29 0 29 6 2 0 70 0 41 0 29 0 59 3 4 0 70 0 41 0 29 0 118 6 8 0 7...

Страница 35: ...Combi Port E D Installation and operation manual 35...

Страница 36: ...to make changes without prior notification to the specification of incorporated components in line with its policy of continuous improvement and development www uponor com 1105741 v1_03_2020 Producti...

Отзывы: