Technical data 

 

1.5.1

 

Fera 60 

 

 

Model 

 

NL

BE/FR

 

DE

AT/CH/GB/IT

Propane

Type 

 

C11 / C31

C11 / C31

 

C11 / C31

C11 / C31

C11 / C31

Gas / P

 

G20 / 20 mbar

 

G20 / 20 mbar 

G25 / 25 mbar

G25 / 25 mbar

 

G25 / 20 mbar 

G20 / 20 mbar

G30/37 mbar

Gascat.

 

I2L

I2E+

 

I2ELL

I2H

I3P

Input / output

 

6,9 kW / 4,31kW

7,27 kW / 2,81 kW

 

6,14 kW / 2,48 kW

6,0 kW / 3,8kW

Max/min

 

0,85/0,29 m3/h

0,77/0,30 m3/h

 

0,76/0,31 m3/h

0,24 /0,09 m3/h

Branderdruk 

 

23,8 mbar

18,8 mbar

 

19,0 mbar

36,7 mbar

7,27 kW / 2,81 kW

0,77/0,30 m3/h

18,8 mbar

 

 

1.5.2

 

Fera 75 

  

 

 

Model 

 

NL

BE/FR

 

DE

AT/CH/GB/IT

Propane

Type 

 

C11 / C31

C11 / C31

 

C11 / C31

C11 / C31

C11 / C31

Gas / P

 

G20 / 20 mbar

 

G20 / 20 mbar 

G25 / 25 mbar

G25 / 25 mbar

 

G25 / 20 mbar 

G20 / 20 mbar

G30/37 mbar

Gascat.

 

I2L

IE2+

 

I2ELL

I2H

I3P

Input / output

 

8,1 kW / 5,7 kW

8,9 kW / 6,2 kW

 

7,2 kW / 4,8 kW

8,9 kW / 6,2 kW

7,7 kW / 5,1kW

Max/min

 

0,99/0,53 m3/h

0,94/0,54 m3/h

 

0,89/0,51 m3/h

0,94/0,54 m3/h

0,31 /0,16 m3/h

Burner pressure 

 

24,0 mbar

18,4 mbar

 

18,6 mbar

18,4 mbar

36,7 mbar

 

 

 

1.5.3

 

Fera 75 corner 

 

  

 

Model 

 

NL

BE/FR

 

DE

AT/CH/GB/IT

Propane

Type 

 

C11 / C31

C11 / C31

 

C11 / C31

C11 / C31

C11 / C31

Gas / P

 

G20 / 20 mbar

 

G20 / 20 mbar 

G25 / 25 mbar

G25 / 25 mbar

 

G25 / 20 mbar 

G20 / 20 mbar

G30/37 mbar

Gascat.

 

I2L

IE2+

 

I2ELL

I2H

I3P

Input / output

 

11,9 kW / 4,8 kW

12,6 kW / 4,6 kW

 

10,6 kW / 4,8 kW

12,6 kW / 4,6 kW

11,7 kW / 5,0 kW

Max/min

 

1,46/0,59 m3/h

1,34/0,48 m3/h

 

1,30/0,59 m3/h

1,34/0,48 m3/h

0,48 /0,20 m3/h

Burner pressure 

 

23,4 mbar

18,6 mbar

 

18,6 mbar

18,6 mbar

34,5 mbar

 

 

 

 

 

14

1.5.4

 

Fera 105 

 

 

Model 

 

NL

BE/FR

DE

AT/CH/GB/IT

 

Propane

 

Type 

 

C11 / C31

C11 / C31

C11 / C31

C11 / C31

C11 / C31

 

Gas / P

 

G20 / 20 mbar

G20 / 20 mbar 

G25 / 25 mbar

G25 / 25 mbar

G25 / 20 mbar 

G20 / 20 mbar

 

G30/37 mbar

 

Gascat.

 

I2L

IE2+

I2ELL

I2H

I3P

 

Input / output

10,2 kW / 7,6 kW

10,4 kW / 7,8 kW

8,9 kW / 6,3 kW

10,4 kW / 7,8 kW

 

10,4 kW / 7,7kW

 

Max/min

 

1,25/0,63 m3/h

1,1/0,65 m3/h

1,09/0,64 m3/h

1,1/0,65 m3/h

 

0,42 /0,16 m3/h

 

Burner pressure 

23,0 mbar

18,2 mbar

19,5 mbar

18,2 mbar

36,1 mbar

 

 

 

 

1.5.5

 

Fera 140 

 

 

Model 

 

NL

BE/FR

DE

AT/CH/GB/IT

 

Propane

 

Type 

 

C11 / C31

C11 / C31

C11 / C31

C11 / C31

Gas / P

 

G20 / 20 mbar

G20 / 20 mbar 

G25 / 25 mbar

G25 / 25 mbar

G25 / 20 mbar 

G20 / 20 mbar

 

Gascat.

 

I2L

IE2+

I2ELL

I2H

Input / output

13,0 kW / 4,4kW

13,3 kW / 5,6 kW

11,3 kW / 4,6 kW

13,3 kW / 5,6 kW

 

Max/min

 

1,60/0,54 m3/h

1,40/0,59 m3/h

1,39/0,57 m3/h

1,40/0,59 m3/h

 

Burner pressure 

23,3 mbar

18,3 mbar

18,4 mbar

18,3 mbar

N.A. 

 
 

Содержание Fera 105

Страница 1: ...ATERIAL 16 2 2 THE FERA 60 75 AND 105 16 2 2 1 THE CONNECTIONS 16 2 2 2 POSITIONING OF THE CHIPS MOULDED FIRE BRICKS WHITE STONES AND LOGS 17 2 2 3 MOUNTING OF THE CONVECTION SET FOR THE FERA 23 2 2 4...

Страница 2: ...ADIO 50 6 WARRANTY CERTIFICATE 51 6 1 WARRANTY CONDITIONS 52 6 2 THE WARRANTY IS NOT APPLICABLE IN THE FOLLOWING CASES 53 4 Introduction The closed built in gas fire which you have just purchased from...

Страница 3: ...or a supply of fresh air and the flue gases are conveyed directly to the outside via the internal pipe Figure 1 Wall duct with cage 6 1 1 Flue requirements With the Fera you have a choice of two types...

Страница 4: ...ed depending on the wall thickness Firstly fit a 1 m piece onto the fire s connection collar fit the 90 bend to this piece and if necessary shorten the wall duct to the desired length and connect it t...

Страница 5: ...on air Always check the existing chimney on leakage otherwise the balanced flue system won t work If the existing chimney is in a bad condition we prefer to use two flexible flues The outer flue is fo...

Страница 6: ...90 bend upwards The flue then extends for 1 metre upwards to a roof duct 1 metre vertical 1 metre 90 bend 2 metres 0 5 metres horizontal 0 5 1 5 0 75 metres 90 bend 2 metres 1 metre vertical 1 metre R...

Страница 7: ...1 C11 C31 Gas P G20 20 mbar G20 20 mbar G25 25 mbar G25 25 mbar G25 20 mbar G20 20 mbar G30 37 mbar Gascat I2L IE2 I2ELL I2H I3P Input output 11 9 kW 4 8 kW 12 6 kW 4 6 kW 10 6 kW 4 8 kW 12 6 kW 4 6 k...

Страница 8: ...here must be any flammable material within the area of the fire If mounting is carried out using materials known in the industry which have an insulating effect such as for example Promatect Nobranda...

Страница 9: ...ough the chips will produce a thinner chip which will glow more Tip 2 Before putting the chips in place it is best to position the rearmost log first and also the two logs on either side The chips can...

Страница 10: ...et of logs is to be positioned as follows Figuur 5 Houtstammetjes Fera 60 1 3 2 4 1 3 4 2 Figure 5 Fera 60 logs 20 For the Fera 75 This is the set of logs you have received The set of logs is to be po...

Страница 11: ...t of logs is to be positioned as follows 5 2 6 3 1 4 Figure 7 Fera 75 corner logs 1 2 3 5 4 6 7 11 10 8 9 7 8 9 10 11 22 For the Fera 105 This is the set of logs you have received The set of logs is t...

Страница 12: ...ase of installation in a natural stone mantel piece depending on the type of natural stone we still advise using the convection sets so that not all the heat affects the natural stone Figure 9 convect...

Страница 13: ...e loosened by means of the screws at the inside and remounted after everything has been finished 10 For putting the front cap back into place wear the supplied white gloves in order to avoid possible...

Страница 14: ...rom the stove by lifting it up 2 Carefully take out the Fera appliance from the main frame and put it aside in a safe place 3 Take the main frame from the stove off the pallet and drill a hole in the...

Страница 15: ...pliances with manual control ultrasound remote control and radio remote control 3 1 Manually controlled appliances 3 1 1 Lighting the burners Make sure the gas tap is turned on The main burner in the...

Страница 16: ...the gas tap is turned on The main burner in the fire is ignited by a pilot light which in turn is ignited by a piezo element Once the pilot light is lit it heats up a thermocouple which creates a sma...

Страница 17: ...n the two contacts Plug into the electric socket and turn on the gas tap 3 3 1 Lighting the burners When the Big flame Figure 14 no 1 and the Off knob no 3 are pushed in simultaneously two knob igniti...

Страница 18: ...y pressing the ON and OFF knob 3 3 2 Extinguishing the burners To completely extinguish the fire press the OFF knob Figure 14 no 3 on the transmitter and the main burners as well as the pilot light wi...

Страница 19: ...37 38...

Страница 20: ...39 40...

Страница 21: ...41 42...

Страница 22: ...43 44 Fera 75 corner RIGHT...

Страница 23: ...45 Fera 75 corner LEFT 46...

Страница 24: ...continuously Check that the gas tap is turned on or whether there is a blockage in the gas supply The thermocouple is broken Contact your dealer Is the ignition knob turned on fully It must be turned...

Страница 25: ...y on Burner bed comes on The Fura burns very blue It needs 30 minutes in order to heat up completely Please contact your dealer about other problems Check that the gas tap is turned on or whether ther...

Страница 26: ...ear starting on the date of purchase which must be clearly and distinctly stated on the sales invoice The attached warranty registration card should be carefully completed and returned to Kal Fire B V...

Страница 27: ...whatsoever are made to the appliances 4 If the owner of the appliance changes 5 If the appliance is not installed in accordance with the installation instructions and or not used in accordance with th...

Отзывы: