12.3
Uninstalling the device
DANGER
Dangerous voltage due to two operating voltages
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. The dis-
charge time of the capacitors is up to 5 minutes.
1. Only appropriately qualified electricians authorised by the mains supply network operator are permitted to
open and maintain the device.
2. Before opening the device: Disconnect the AC and DC sides and wait at least 5 minutes.
↻
Device shut down and no voltage is present.
↻
AC cable disconnected [See section 12.2.1
↻
DC connection disconnected [See section 12.2.2
1. Undo the cable fitting for Ethernet cables [ W_29].
2. Undo the cable fitting for RS485 cables [ W_20].
3. Disconnect the plug from the communication circuit board.
4. Remove the interface cables from the device.
5. Insert the sealing plug in all open cable fittings.
ð
The device has been uninstalled. Proceed with removal.
12.4
Disassembling the device
↻
Unit has been switched off and uninstalled.
1. Remove the screw that prevents the device from being lifted off the mount.
2. Use the lateral openings and lift the device off the mount.
ð
Device removed. Proceed with the packaging process.
12.5
Packaging the device
↻
Device has been uninstalled.
1. If possible, always pack the device in the original packaging. If this is no longer available, an alternative is to
use equivalent packaging.
2. You must be able to close the box completely and it must be able to accommodate the weight and size of
the device.
12.6
Storing the device
NOTE
Property damage as a result of condensation
Faulty storage can form condensate in the device and impair the device functioning (e.g. storage outside the
ambient conditions or temporary relocation from a cold to a hot environment).
1. Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently be-
fore installation.
2. Store in accordance with the technical data > Environmental data
↻
Device packaged.
F
Store the device at a dry location, in accordance with the ambient temperature range Environmental data.
12 | Decommissioning and dismantling