1. Insert the Ethernet cable into the machine and the machine's control cabinet, using an EMC
connection.
2. Lead the Ethernet cable through the cable ducts to SIGMA CONTROL 2. Use the wiring path
in the 24V range (blue wiring) of the ducts.
3. Attach the RJ45-plug to the cable end.
4. Plug the RJ45 plug into the Ethernet interface X1 of the SIGMA CONTROL 2 until it latches.
For connecting the machines to a network (LAN) or switch:
Connect the Ethernet cable for each machine to the LAN connection or switch.
1. Attach the RJ45-plug to the cable end.
2. Plug the RJ45plug into the network socket until it latches.
8.7.4.2 Setting the controller of machine 1 as master
Precondition The electrical connection is made.
Access level 2 is activated.
Master IP configuration
If the controllers of both machines are linked directly, they must be given different IP addresses.
Example:
■ IP addressController machine 1 (Master mode): 169.254.100.101
■ IP address Controller machine 2 (Slave): 169.254.100.102
Precondition The electrical connection is made.
Access level 2 is activated.
1. Set IP address for the master see chapter 8.2.14,IP address see above example.
The IP address of machine 1 (master) is set correctly.
2. Open the 8.1.2.1
<Communication – Ethernet/SIGMA NETWORK – Connections – SIGMA
CONTROL 2> menu.
3. Use «Up» or «Down» to select the
Mode line.
4. Press «Enter».
The setting mode is active.
5. Use «Up» or «Down» to set Machine 1
Master operating mode.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
8.1.2.1 SIGMA CONTROL 2
Menu
Status
Run
1¦Error
0
------------------------------
Mode
:
Master
Active line
Port
:
2.001
······························
Communication partner
6. Press the «Enter» key.
The setting is applied.
8
Initial Start-up
8.7
Setting the machine for master control operation
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
119