EPC
Current
drawn [A]
Direct start
Star-delta start
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
1000-2-G
10.4
●
20
4 x 1.5
–
–
● Pressure switch
○ controller (START CONTROL)
Tab. 19 Supply details 690V / 3 / 50Hz
Mains frequency: 60Hz
Rated voltage: 230V±10% / 3 / 60Hz
EPC
Current
drawn [A]
Direct start
Star-delta start
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
150-2-G
4.6
●
10
4 x 1.5
–
–
230-2-G
6.9
●
16
4 x 2.5
–
–
420-2-G
10.9
●
20
4 x 2.5
16
4 x 2.5
550-2-G
17.4
○
35
4 x 6
20
4 x 2.5
750-2-G
21.0
○
50
4 x 10
25
4 x 4
1000-2-G
28.0
○
63
4 x 16
35
4 x 6
● Pressure switch
○ controller (START CONTROL)
Tab. 20 Supply details 230V / 3 / 60Hz
Rated voltage: 380V±10% / 3 / 60Hz
EPC
Current
drawn [A]
Direct start
Star-delta start
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
150-2-G
2.8
●
6
4 x 1.5
–
–
230-2-G
4.2
●
10
4 x 1.5
–
–
420-2-G
7.1
●
16
4 x 2.5
10
4 x 1.5
550-2-G
10.5
●
20
4 x 2.5
16
4 x 2.5
750-2-G
12.5
●
25
4 x 4
16
4 x 2.5
1000-2-G
19.0
○
35
4 x 6
20
4 x 2.5
● Pressure switch
○ controller (START CONTROL)
Tab. 21 Supply details 380V / 3 / 60Hz
2
Technical Specifications
2.11 Electrical connection
No.: 9_5753 24 E
Assembly and operating manual 2-stage piston compressor
EPC-2-G
11
Содержание EPC 150-2-G
Страница 2: ...KKW PEPC 2 04 en SBA KOLBEN AGGREGAT 2 STUFIG 20170303 120300...
Страница 6: ...Contents iv Assembly and operating manual 2 stage piston compressor EPC 2 G No 9_5753 24 E...
Страница 10: ...List of Tables viii Assembly and operating manual 2 stage piston compressor EPC 2 G No 9_5753 24 E...
Страница 100: ...13 Annex 13 2 Dimensional Drawing 90 Assembly and operating manual 2 stage piston compressor EPC 2 G No 9_5753 24 E...