DP02-72

Under Voltage Protection

Over Frequency 
Protection

Under Frequency 
Protection

TRUE RMS

Latch Function

Voltage      (V)
Current      (A)
Frequency (Hz)

Over Voltage Protection

Under Current Protection

Over Current Protection

Volt

V

Hz

Hz

V

Hz

Display Functions

18 16

15

Digital Protector

One phase 
Voltage – Current
         and 
Frequency control

General:

In one phase systems, it measures RMS values of AC voltage,
current and system frequency sensitively. 
DP02-72 has many  features. 
Those are;

- Over Voltage Protection

(o - U)

- Under Voltage Protection

(u - U)

- Over Current Protection

(o - C)

- Under Current Protection

(u - C)

- Over Frequency  Protection

(o - F)

- Under Frequency  Protection

(u - F)

When device is turn on if its adjusted voltage and frequency in its 
interval relay  switch on.
If any of error occurred at the end of adjusted time relay switch off 
its contact. When system return normal  values, at the end of time 
out relay switch on.

IMPORTANT:

  L - N  is device supply inputs. 

Thus,the applied L – N voltage must be 
rated voltage of  system . Otherwise normal 
led makes flash and the device switched off 
its output contact.
The measured frequency also  must the  
frequency  of the system.

Special Buttons:

Select: 

(Up direction) 

when pressing continuously, 
screen displays  frequency of 
system. When button release 
device continue to show voltage. 

Reset: 

If error case although disappeared 
then device is not return to normal, 
latch-function occurred and it 
makes locked device. 
Or Lock-function (only for currents) 
may be occured.
After checking error in system then 
restart device with pushing reset 
button.

V

Re

t

t

t-1

(o-U)

(u-U)

r-t

t-1

r-t

Umax

Umin

Under Voltage

Over Voltage

VL

Normal

Normal

Over and Under Voltage :  (o-U),(u-U)

Under voltage (u-U)   it can adjusted between Umin= (180 – 225 V).
Over voltage    (o-U) it can adjusted between   Umax=(235 –275 V).
If the voltage drops below the adjusted under voltage limit, when 

u-U 

shows

 

on the screen and device switch off its output contact end of the  

t-1 time Normal LED  turned on .In this case 

u-U 

warn appears on the 

screen.
If the voltage exceed the adjusted over voltage limit, Normal LED 
turned off and output relay switch off. In this case 

o-U 

warn

 

appers on

 

its screen.
Hysteresis is 6 V.

I(A)

Re

t

t

Sdt 

d-t

r-t 

d-t

r-t 

o-C

u-C

%hYS

%hYS

Over and Under Current :  (o-C),(u-C)

Under Current (u-C)   
Over Current   (o-C)  
When the current of the protected system goes below the adjusted 
value it switches off its output contact after 

d-t 

delay.

Normal LED turn off  and relay switch off its contact .In this case 

u-C 

warn appears

 

on display.

When current passing through phase of the protected system 
exceeds the adjusted value the device switches off its output contacts 
after a proper time (

d-t

).Normal LED turn off  and relay switch off its 

contact .In this case 

o-C 

warn appears

 

on display.

NOTE: 

Under current protection set value with its hysteresis must not 

overlap with over current protection set value with its hysteresis or, the 
under current protection set value must not be higher than the over 
current protection set value.

VOC

OC

r-t 

r-t 

Start delay time: Sd-t 

It can be set between 1 and 60 seconds.It is used to prevent the switch 
off from occurance because of the motor's inrush current.
This function can be disable if Sd-t value = 000 (oFF)

Return Time : r-t

it shows the delay time that device will wait to switch on its output relay 
when failure ends after a switch off. It can be set between 0,5 and 99,9 
seconds.

Very Over Current Coefficient : VOC (

Current Very Sudden Switch 

Off Protection)
It can be set by the user between 2,1 and 6. 
When the current value exceeds the adjusted value within the start 
delay time, the device switches off, its output contact immediately.
Very Over Current value = (o – C) x (VOC)
This function can be disable if VOC = 000 (oFF)

Over Current Coefficient : OC (

Current Sudden Switch Off Protection)

It can be set by the user between 1,1 and 2. 
When the current value exceeds the adjusted value without the start 
delay time, the device switches off, its output contact immediately.
Over Current value = (o – C) x (OC)
This function can be disable if OC = 000 (oFF)