L3 (T)
L2 (S)
L1 (R)
N
lL3
lL2
lL1
max.
demand
Pulse
Reac.
(C)
ENERGY-11-DIN
Output Pulses
20 21 22
C1 O1 O2
▼ ▼ ▼
N L1 L2 L3
k1
l1
k2
l2
k3
l3
230 Vac
50-60Hz
Voltage Inputs
0 – 500 Vac
Current Inputs
X/5 A
▲ ▲ ▲ ▲
Power
Supply
▲
▲
L3 (T)
L2 (S)
L1 (R)
N
max.
demand
Pulse
Reac.
(C)
ENERGY-11-DIN100A
Output Pulses
20 21 22
C1 O1 O2
▼ ▼ ▼
N L1 L2 L3
k1
l1
k2
l2
k3
l3
230 Vac
50-60Hz
Voltage Inputs
0 – 500 Vac
Current Inputs
100 A
▲ ▲ ▲ ▲
Power
Supply
▲
▲
lo
ad
With 100A current transformers
Act 0039230.0
W VAR VA Hr
K
G
M
Act - 0000000.0
W VAR VA Hr
K
G
M
imp exp
∑
imp exp
∑
Total import Active Energy
Total export Active Energy
M
EA
SU
R
EM
EN
TS
SET
SET
pos 0009230.0
W VAR VA Hr
K
G
M
neg - 0000065.3
W VAR VA Hr
K
G
M
imp exp
∑
imp exp
∑
Reactive Energy (KVARhr,MVARhr,GVARhr)
Total import/export positive and negative energy can be monitored .
Energies can be deleted in (CLR Energy) menu.
Total import positive Reactive Energy
Total import negative Reactive Energy
SET
SET
pos 0000000.0
W VAR VA Hr
K
G
M
neg - 0000000.0
W VAR VA Hr
K
G
M
imp exp
∑
imp exp
∑
Total export positive Reactive Energy
Total export negative Reactive Energy
SET
SET
App= 0039230.0
W VAR VA Hr
K
G
M
imp exp
∑
Total Apparent Energy
Apparent Energy (KVAhr)
Apparent Energy can be deleted in (CLR Energy) menu.
K
G
M
Act 0039230.0
Act 0039230.0
W VAR VA Hr
imp exp
∑
K
G
M
Act 0039230.0
Act 0039230.0
W VAR VA Hr
imp exp
∑
■ The connections of the system must be made when it is out of power.
■ The connections of the device shall be connected as shown in the connection scheme.
■ The current and voltage connections shall be connected in a manner that they are placed on the same phase same current transformer and with the same
direction. Connection scheme must be observed.
■ The value of the current transformer chosen shall not be less than the real load value and X/5 amperes. Moreover, it is recommended to chose class 0,5.
■ Fuses to be used shall be FF type. Fuses to be used shall be chosen according to given current values.
■ Do not supply power to the device before all the connections are checked by means of a measurement apparatus.
■ The terminals for currents and voltage are suitable for cables with 2,5mm2 cross- section.
■ Pulse outputs terminals are suitable to max. 1,5 mm2 cables
Making the Connections
lo
ad
MEASUREMENTS:
(P.F, W, VAr, VA, ΣW, ΣVAR, ΣVA, ΣWh, ΣVArh, ΣVAh )
The above parameters can be reached step by step using arrow keys. Related leds lights up and displays the
corresponding parameter value which is displayed at the same time.
Active Energy (KWhr,MWhr,GWhr)
Total import and export active energy can be monitored. Energies can be deleted in (CLR Energy) menu.
Total import Active Energy