4
Technical data
4.1
Electrical data
blueplanet gridsave
92.0 TL3-S
110 TL3-S
137 TL3-S
DC Input levels
Input levels (DC)
Working range
668-1,315 V
801-1,315 V
1002-1,315 V
Max. DC voltage
1,450 V
Starting voltage
668 V
801 V
1,002 V
Max. input current
145 A
Max. short-circuit current (ISC
max.)
300 A
Polarity safeguard
option / with PCU yes
String fuse
M yes / L yes / XL yes
M yes/ L yes / XL yes
DC- fuse holder
no
DC+ fuse holder
Optional
Number of strings
1
blueplanet gridsave
92.0 TL3-S
110 TL3-S
137 TL3-S
AC Output levels
Output levels (AC)
Nominal power
92 kVA
110 kVA
137 kVA
Nominal voltage
400 V (3P+PE)
480 V (3P+PE)
600 V (3P+PE)
Voltage range: continuous op-
eration
300 V - 580 V
480 V - 760 V
Max. voltage range (up to 100
s)
625 V
825 V
Nominal current
3 x 132.3 A
Max. continuous current
3 x 132.3 A
Contribution to peak short-cir-
cuit current ip
193 A
Initial short-circuit alternating
current (lk” first single-period
effective value)
137 A
Short circuit current continu-
ous [ms] (max output fault
current)
134 A
Inrush current
5 A [RMS (20ms)]
Nominal frequency
50/60 Hz
Frequency range
45 - 65 Hz
Reactive power
0-100 % Snom
cos phi
0.3 - 1 ind/cap
Number of feed-in phases
3
Distortion factor (THD)
< 3 %
AC overvoltage protection
Base
4 | Technical data
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 12