Reactive power control
Reactive power can be used in electrical energy supply networks to bolster the level of voltage. As such, feed-in
inverters can contribute to statistical voltage stability. Reactive power brings about a voltage drop at the induc-
tive and capacitive components of the equipment which can either bolster or reduce the level of voltage. If the
generating plant draws inductive reactive power while active power is being fed in, part of the voltage swing
caused by the active power feed can be compensated for by the supply of reactive power.
This reactive power mode and the respective control process are specified by the grid operator. If no control
process has been specified, then the plant should be operated using a reactive power specification of 0%.
10.1.1 Operating power range depending on grid voltage
The device can be operated within the respective fixed voltage range provided. The maximum apparent power
is stated in the following table. In the event of undervoltage determined by the maximum continuous current
subject to the grid voltage.
The following figures show the reactive power operating range subject to active power and the apparent power
operating range subject to the grid voltage for various devices.
bp gs 92.0 TL3-S
Spannung mit U
N
400V
bp gs 110 TL3-S
Spannung mit U
N
480V
bp gs 137 TL3-S
Spannung mit U
N
600V
Maximale Scheinleistung
[p.u.]
≥ 400
≥ 480
≥ 600
1,0
380
456
570
0,95
360
432
540
0,90
340
408
510
0,85
Tab. 6:
Maximale dauerhafte Scheinleistung in Abhängigkeit der Netzspannung
P [p.u.]
Q [ P.u]
0,6
0,4
0,2
0
1
0,8
1,2
0,6
0,6
0,0
underexcited
overexcited
1
1
0,8
1
1,2
0,4
0,6
0,2
feed-in
charge
above U
N
at 0,9 U
N
at 0,8 U
N
above U
N
at 0,95 U
N
at 0,9 U
N
at 0,85 U
N
Fig. 47:
P-Q Betriebsbereich für bp gridsave 92.0 TL3-S
580
S [p.u. S
nom
]
U [V]
0,6
0,4
0,2
0
1
0,8
1,2
380
500
340
300
420
460
540
Nominal
capability
OVRT
U
V
R
T
Under voltage
derating
Disconnection
Fig. 48:
Scheinleistungsabhängigkeit der Netzspannung für
bp gridsave 92.0 TL3-S