Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Settling time
1000 – 12000 [ms] /
5000 [ms] / 10
F
Set the settling time in the event of an abrupt change in the reactive
power target value.
4
1
2
3
4
Port
F
Set up the port at which the webserver can be reached.
4
1
2
3
4
Q Setpoint
NOTE: Define Q Setpoint
4
1
2
3
4
Reactive power set-
point
0 - 100 [% VarMax] /
0 [% VarMax]/ 0.0
F
Set reactive power Q to a fixed value.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
1. Maximum change in the reactive power in the event of a change to
over-excited mode.
2. Maximum change in the reactive power in the event of a change to
under-excited mode.
4
1
2
3
4
Settling time
1000 – 12000 [ms] /
5000 [ms] / 10
F
Set the settling time in the event of an abrupt change in the reactive
power target value.
4
1
2
3
4
Control Mode Reactive
Power
Off / 0 / 1 / Off
F
Select reactive power specification.
- 0 = No reactive power
- 1 = Set reactive power to a fixed value
Reactive power acti-
vated
0 / 1
F
All set values are transferred and used with 1.
4
1
2
3
4
External grid protection
disconnection
NOTE: Option to detect the external grid protection devices
4
1
2
3
4
External grid protection
Status
F
Select the device.
4
1
2
3
4
DC Disconnection
NOTE: When the function is deactivated, a connected
Powador-protect and received signal, will not trigger an inter-
ruption of the DC component.
F
Activate DC shutdown on every error. Thus, the DC supply is also dis-
connected.
4
1
2
3
4
Relay
NOTE: Opportunity to configure the fault signal relay [ERR].
4
1
2
3
4
Relay
Positive logic | Neg-
ative logic
inactive | active
1. Select the type of logic.
2. Select the form of activity.
3. Confirm the action field.
4
1
2
3
4
EMS Communcication-
Timeout
NOTE: The menu item is only available for EMS in the battery.
4
1
2
3
4
Operating mode
ON | OFF
F
Switch on the function for monitoring the system.
4
1
2
3
4
Zeit
30 s 1 – 600 [s]
F
Define time of interruption until signal must appear at least.
9 | Configuration and operation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 60
EN-US