Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Status Leistungsteil
NOTE: View the status of the power unit
4
1
2
3
4
Requested state
Mode: Off, Standby,
Connected
Connection status:
see in the "SunSpec Information Model Reference
KACO" document under Model- 64201 "enum16" as well as in the Inte-
gration Manual.
4
1
2
3
4
Column: Local
The unit reacts to the local values specified via the web interface.
.
Column: EMS
Unit reacts to the values sent by the EMS.
Column: Active
Unit reacts to the status of the power unit.
4
1
2
3
4
Current status
Displays system status.
4
1
2
3
4
Buttons in the menu:
Device control
NOTE: Save settings for watchdog, battery limits, P and Q set-
ting.
Reset
F
Reset to default value
or
Apply and save
F
Set and save value
or
Apply
F
Take over parameters for current session.
4
1
2
3
4
Watchdog Zeit
NOTE: Possibility to monitor the entire system
4
1
2
3
4
Lokal / EMS / Active
30[s]
F
Set time for monitoring the connection.
4
1
2
3
4
Battery limits (tempo-
rary)
F
NOTE: Possibility to set the battery limits
4
1
2
3
4
Minimum discharge
voltage
0.1
F
Set the minimum discharge voltage.
Maximum discharge
current
0.1
F
Set the maximum discharge current.
Minimum discharge
current
NOTE: Not supported!
Maximum charge volt-
age
0.1
F
Set maximum charging voltage.
Maximum charge cur-
rent
NOTE: Not supported!
Minimum charge cur-
rent
0.1
F
Set the minimum charging current for the battery.
4
1
2
3
4
Battery limits enabled
0 / 1
F
All set values are transmitted and used with 1.
4
1
2
3
4
P Setpoint
NOTE: Define active power specification
4
1
2
3
4
Setpoint active power
0 – 100 [% Pmax]/
0 [% Pmax] 0.1
F
Set the setpoint of the active power.
4
1
2
3
4
Power gradient in-
creasing & power gra-
dient decreasing
1 – 65,534 [% Slim /
min] / 65,534 / 1
1. Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode.
2. Maximum change in the reactive power %S
lim
/min in the event of a
change to under-excited mode.
Manual
Configuration and operation | 9
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 59