Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
External
NOTE: The output power of the device can be set permanently
to a lower value than the maximum output power by the ex-
ternal power limitation.
4
1
2
3
4
Power Limitation
Status
F
Specify the activation status.
4
1
2
3
4
AC fallback active
power
0 – 100 [%Plim] /
100 [%Plim] / 1
F
Set fallback power.
Specifies the standard power in the event of a communication failure. If
no active power command is received within the configured fallback
time, the device sets the power to the configured fallback power.
4
1
2
3
4
Fallback time
0 – 43200 [s] /
300 [s] / 1
F
Set the fallback time for the external power specification.
WARNING! After the set fallback time, external (RS485 or
Modbus) specifications for cos-phi, Q and P are reset to the
respective set fallback value (cos-phi constant, Q-con-stant or
fallback power).
NOTE: If the fallback time is set to 0s, external settings for
cos-phi, Q and P are not reset (operation continues with the
last received setpoint).
4
1
2
3
4
Reactive Power Control
(RPC)
NOTE: Activate the reactive power process in the mode menu.
More detailed information at:
4
1
2
3
4
Mode
Cos-phi const. | Q
const. | Cos-phi(P/Pn)
| Q(U)
Password protection
Status
1. Select a control process.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Cos-phi constant
NOTE: Define the cos ϕ constant.
4
1
2
3
4
cos-phi const.
0,3 – 1 / 1 /
0,001
F
Determine the specified power factor.
4
1
2
3
4
Power gradient in-
creasing & power gra-
dient decreasing
1 – 65,534 [% Slim /
min] / 65,534 / 1
1. Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode.
2. Maximum change in the reactive power %S
lim
/min in the event of a
change to under-excited mode.
4
1
2
3
4
Settling time
1,000 – 120,000
[ms] / 5,000 [ms]
10
Password protection
Status
1. Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump).
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Q constant
NOTE: Define the Q constant.
9 | Configuration and operation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 52
EN-US