Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Connection Conditions
NOTE: According to their network conditions, exact connec-
tion conditions must be set.
4
1
2
3
4
Min. conn. voltage af-
ter grid mon.
10 – 110 [% Unom] /
0.1 &
Max. conn. voltage af-
ter grid mon.
90 – 125 [% Unom] /
0.1
F
Specify switch-on voltage range after grid error.
4
1
2
3
4
Min. conn. frequency
after grid mon.
45 – 65 [Hz] / 0.01
&
Max. conn. frequency
after grid mon.
45 – 65 [Hz] / 0.01
F
Specify switch-on frequency range after grid error.
4
1
2
3
4
Min. conn. voltage af-
ter grid failure
10 – 110 [% Unom] /
0.1 &
Max conn. voltage af-
ter grid failure
90 – 125 [% Unom] /
0.1
F
Specify switch-on voltage range after grid error.
4
1
2
3
4
Min. conn. frequency
after grid failure
45 – 65 [Hz] / 0.01
&
Max. conn. frequency
after grid failure
45 – 65 [Hz] / 0.01
F
Specify switch-on frequency range after grid error.
4
1
2
3
4
Monitoring time grid
voltage
1000 - 1800000
[ms] / 60000 /
1000
&
Monitoring time PV
voltage
1000 - 1800000
[ms] / 60000 /
1000
F
Zeit für die Beobachtung der Netzspannung und PV-Spannung
definieren.
4
1
2
3
4
Waiting time after grid
failure
1000 - 1800000
[ms] / 60000 /
1000
Password protection
Status
1. Set waiting time after grid error.
2. Activate optional password protection.
3. Confirm the action field.
9 | Configuration and operation
Manual
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
Page 46
EN-US