9.4.2
Configuration via web user interface
Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Overview
Input screens for basic settings
4
1
2
3
4
Language
(11 languages)
1 Select the desired language for the user interface.
2 Confirm the action field.
4
1
2
3
4
Localization
Status
1 Select the current date and enter the time or press the button "Sync
with client device now".
2 Select a time zone.
3 Activate the NTP server and assign a name.
4 Obtain NTP server settings from DHCP.
5 Specify the temperature unit.
6 Confirm the action field.
4
1
2
3
4
Miscellaneous
1 Enter the device name.
2 Enter the degree of longitude and latitude of the installation loca-
tion.
3 Enter the plant ID.
4 Confirm the action field.
4
1
2
3
4
DC Parameter
Input screens for generator and string collector.
4
1
2
3
4
String Combiner
NOTE: Opportunity to configure a string collector.
String combiner moni-
toring
Status
F
Select the monitoring function when the string collector is con-
nected.
Serial number of the al-
located string collector
F
Enter the serial number once the device has been installed.
NOTE: The serial numbers of the string collector that are not con-
nected directly to the device are entered on the segment controller.
Baud rate & number of
data capture units
9600
8n1
1 Specify the baud rate and capture interval.
2 If necessary, enter the number of the data capture unit.
Unit address
Unit channels
1 Specify the IP address of the string collector.
2 Specify the number of monitored strings.
3 Confirm the action field.
4
1
2
3
4
Constant voltage mode
NOTE: Opportunity to deactivate the MPP seek mode in order to oper-
ate the device with a constant DC voltage.
Constant voltage
875 – 1300 [V]
F
Set value for constant voltage control.
Constant voltage mode
Off | On
1 Activate or deactivate the constant voltage controller.
2 Confirm the action field.
4
1
2
3
4
DC starting voltage
1000 – 1450 [V]
NOTE: The device begins feed-in as soon as this DC voltage is present.
1 Set the starting voltage.
2 Confirm the action field.
4
1
2
3
4
Insulation resistance
100 – 2000 [kOhm]
1 Set threshold value (in 1kOhm steps) at which the insulation moni-
tor reports an error.
2 Confirm the action field.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 49