Page 7
KACO blueplanet 3.0 NX1 M2 KACO blueplanet 3.7 NX1 M2 KACO blueplanet 4.0 NX1 M2 KACO blueplanet 5.0 NX1 M2
Fig. 21.
Select inverter
Fig. 22.
Selecting the desired inverter
Fig. 23.
Set parameters for initial
commissioning / view current values
1.10
Select Country & Grid Code
Under <Available Inverters>, select the
unit and in the <Inverter Values &
Settings> menu, open the <Parameter
Settings> menu <Settings for>.
1.
Select <country / grid code>.
2. Select operator country and network
type according to
network operator
requirements
and confirm with <OK>.
3. Activate additional functions via <enable
functions> - see chapter 4.2 on page 16
Note
: By default, all required parameters
are activated via the respective grid code.
Note:
After changing the grid standard,
the unit performs a self-test. As a result, it
may take approx. 2 minutes until the unit
feeds in.
Note:
If desired by the grid operator or
customer, further grid standard settings
can be made (e.g., setting reactive power,
Q(U) curve, see parameter, chapter 4.3).
Fig. 24.
Check or change country and
grid code
Fig. 25.
select country & grid code -
observe normative requirement!