8
Commissioning
8.1
Requirements
PELIGRO
Lethal voltages are still present in the connections and cables of the device even after the device has be-
en switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
›
The device is only permitted to be commissioned by a qualified professional.
›
Unauthorised persons must be kept away from the device.
↻
The device has been mounted and electrically installed.
↻
The PV generator supplies a voltage above the configured start voltage.
1 Connect the grid voltage using the external circuit breakers.
2 Connect the PV generator using the DC isolator switch (0 > 1)
»
The device begins operation.
»
During initial start-up: Follow the instructions of the New Connection Wizard.
8.2
Preconditions relating to standards
Attachment of safety label in accordance with UTE C15-712-1
The code of practice UTE C15-712-1 requires that, upon connection to the French
low-voltage distribution network, a safety sticker showing a warning to isolate both
power sources when working on the device must be attached to each device.
F
Attach the provided safety sticker to the outside of the device housing where it is
clearly visible.
ATTENTION
Présence de deux
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
Isoler les deux sources
avant toute intervention
Fig. 39:
Safety label UTE C15-712-1
Kaco blueplanet 29.0TL3