8.5
Shutting down for maintenance / troubleshooting
Shutdown sequence
1 Switch off the grid voltage by turning off the external circuit breakers.
2 Disconnect the DC side using the DC isolator switch.
DANGER! The DC cables are still live
»
After shutdown, wait 5 minutes before opening the device.
8.6
Disconnecting the connections
8.6.1
AC connection
↻
A check has been performed to ensure there is no AC/DC voltage present.
↻
Housing cover removed and set to one side.
1 Detach cables (L1/L2/L3) from the AC connection terminal [ W_17].
2 Detach the PE line from the earthing bolt [ W_17].
3 Loosen the cable fitting and pull the cables out through the cable fitting [ W_46].
NOTE: If the AC cable does not fit through the cable fitting due to the size of the cable lug, then the AC cable must
be severed at the cable lug.
4 Place protective caps on the ends of the AC cables.
8.6.2
DC connection
↻
A check has been performed to ensure there is no DC voltage present.
↻
Housing cover removed and set to one side.
1 Detach the line ends from the PV generator at the DC+ and DC- busbar [ W_17].
2 Place the fastening elements back in the fittings bag.
3 Loosen the cable fitting and pull the DC cable through the cable fitting [ W_46].
NOTE: If the DC cable does not fit through the cable fitting due to the size of the cable lug, then the DC cable must
be severed at the cable lug.
4 Place protective caps on the ends of the DC cables.
9
Decommissioning and removal
9.1
Switching off the device
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device has
been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
›
The device must be mounted in a fixed position before being connected electrically.
›
Observe all safety regulations and current technical connection specifications of the responsible power
supply company.
›
The device may only be opened and serviced by an authorized electrician.
›
Switch off the grid voltage by turning off the external circuit breakers.
›
Check that all AC and DC cables are completely free of current using a clip-on ammeter.
›
Do not touch the cables and/or terminals/busbars when switching the device on and off.
›
Keep the device closed when it is in operation.