External 24 V DC power supply
As an alternative to the PoE power supply, the access manager can also be supplied
via an external 24 V DC power source.
NOTICE
Possible damage in case of simultaneous power supply via PoE and 24 V DC
The device can be damaged in case of simultaneous power supply via PoE and exter-
nal supply.
•
Before connecting the external supply, make sure that the device is not supplied
with power via PoE.
Use only power supply units that fulfill the requirements of EN/UL/CSA 60950-1 as
limited power source (LPS).