Connecting the Alarm Input/Output Cables
Menu settings may be required depending on the connected equipment.
The default setting has been set to alarm input (IN:ALARM).
m
Alarm input terminal
Connect the infrared sensor, door sensor, metal sensor, manual switch
sensor and the like.
v
To prevent noise from entering the internal circuit, supply non-voltage
setting signal to the alarm input signal.
v
Do not supply voltage.
v
Using the menu, you can select whether to set to alarm when the
contact is short (MAKE), or when the contact is open (BREAK).
v
Supply such that the alarm signal stays at a minimum of 200 ms or
more. Otherwise, the alarm signal may not be recognized.
.
AUX(IN)
*
GND
Please use a shielded
cable.
m
Alarm output terminal
Connect to alarm devices such as alarm, indicator, light or buzzer.
v
The alarm output signal is open collector output and turns ON during
an alarm. (Maximum voltage 16 V, current 30 mA)
v
This terminal has a polarity. Make sure to connect such that a higher
voltage is output from the + terminal than from the - terminal.
Otherwise, it will result in damages.
.
AUX(OUT)
GND
100
K
Setup
E-19