Table 14: AC Power Cord Specifications
Plug Standards
Electrical Specifications
Country/Region
AS/NZ 3112–1993
250 VAC, 10 A, 50 Hz
Australia
GB2099.1 1996 and GB1002 1996
(CH1-10P)
250 VAC, 10 A, 50 Hz
China
CEE (7) VII
250 VAC, 10 A, 50 Hz
Europe (except Italy, Switzerland, and
United Kingdom)
CEI 23–16/VII
250 VAC, 10 A, 50 Hz
Italy
JIS 8303
125 VAC, 12 A, 50 Hz or 60 Hz
Japan
CEE 7/4
250 VAC, 10A, 50 Hz
Korea
NEMA 5-15
125 VAC, 13 A, 60 Hz
North America
SEV 1011 SEV 6534/2
250VAC, 10A, 50 Hz
Switzerland
BS 1363A
250 VAC, 10 A, 50 Hz
United Kingdom
DC Power Supply in an XRE200 External Routing Engine
An XRE200 External Routing Engine supports two 560 W DC power supplies.
The DC power input (-48 VDC and return) requires a dedicated customer site circuit breaker. We recommend
that you use a two-pole 20-amp DC circuit breaker, or whatever is required by local code.
Each DC power supply contains a single DC power input, status LEDs, an ejector lever, handle, and a fan.