Table 13: Clearance Requirements for the SRX550 Services Gateway
Requirement for Clearance
Recommended
Clearance
Location
Space for service personnel to remove and
install hardware components
8.7 in. (22 cm)
Front of the chassis
Space for service personnel to remove and
install hardware components
17.4 in. (44.2 cm)
Rear of the chassis
Space for cable management and organization
2.5 in. (6.35 cm)
Between front-mounting flange and
rack or cabinet edge
Space for the cooling system to function
properly and to maintain unrestricted airflow
around the chassis
6.0 in. (15.24 cm)
Between both sides of the chassis and
any non-heat-producing surface such
as a wall or cabinet side