NOTE:
The three-phase wye AC PDM must be installed and secured in
the chassis before connecting the power input cables. If the PDM must
be removed, both input power cables must be uninstalled and removed
from the PDM before the PDM can be removed from the chassis. The
MX2008 chassis is not sensitive to phase rotation sequence—either
clockwise or counter clockwise will operate correctly.
To connect wires to the terminal block that serves six PSMs:
a. Insert the grounding wire into the grounding point labeled
GND
.
b. Insert the wire labeled
L1
into the input terminal labeled
A1
.
c. Insert the wire labeled
L2
into the input terminal labeled
B1
.
d. Insert the wire labeled
L3
into the input terminal labeled
C1
.
e. Insert the wire labeled
N
into the input terminal labeled
N1
.
Figure 36: Connecting Power to a Three-Phase Wye AC Power Distribution
Module
g007082
CAUTION:
Wire label configuration is for Juniper Networks supplied cable
only. If you are using your own cable, make sure you use the proper
connections.
Copyright © 2017, Juniper Networks, Inc.
50
MX2008 3D Universal Edge Router Quick Start