When mounting the router in a partially filled rack, load the rack from the bottom to the top, with the
heaviest component at the bottom of the rack.
•
If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the
router in the rack.
•
When removing or installing an electrical component, always place it component-side up on a flat
antistatic surface or in an electrostatic bag.
•
When you install the router, always make the ground connection first and disconnect it last.
•
Wire the DC power supply using the appropriate lugs.
•
Do not work on the system or connect or disconnect cables during electrical storms.
•
Before working on equipment that is connected to power lines, remove jewelry, including rings, necklaces,
and watches. Metal objects heat up when connected to power and ground and can cause serious burns
or become welded to the terminals.
•
Failure to observe these safety warnings can result in serious physical injury.
•
AC power cable warning (Japan):
WARNING:
The attached power cable is only for this product. Do not use the cable
for another product.
Compliance Statements for NEBS
•
The equipment is suitable for installation as part of the Common Bonding Network (CBN).
•
The equipment is suitable for installation in locations where the National Electrical Code (NEC) applies.
•
The battery return connection is to be treated as an isolated DC return (that is, DC-I), as defined in
GR-1089-CORE.
•
You must provision a readily accessible device outside of the equipment to disconnect power. The device
must also be rated based on local electrical code practice.
26
Содержание MX104
Страница 6: ...Figure 2 MX104 Rack Clearance and Chassis Dimensions 6 ...
Страница 8: ...Figure 3 Installing the Front Mounted Router in the Rack 3 1 Mounting screws Rack 2 MX104 router 8 ...
Страница 11: ...Figure 4 Grounding Points on the MX104 Router 2 1 Screws Grounding cable lug 11 ...
Страница 20: ...Figure 11 Connecting a DC Power Cable to an MX104 DC Power Supply 20 ...