Grounding ring lug with hole sized for an M5 screw
•
M5 nut and washer (one per DC power supply, attached)
•
DC power source cables, minimum 14 AWG or as required by local code (not provided)
•
DC power ring lugs, Panduit PV12-14HDRB-2k (two per DC power supply)
•
M6 screws and washers (two per DC power supply, attached)
•
Grounding cable, use 6-AWG (13.3 mm
2
) 60
°
C wire for 24V DC (not provided)
The DC power supply has two terminals on each power supply, covered by a clear plastic cover.
Table 1: MX104 DC Power System Input Voltage
Specification
Nominal Voltage
Operating range: +18 to +30 VDC
+24
Operating range: –39 to –56 VDC
–48
Operating range: –39 to –72 VDC
–60
1. Switch off the dedicated customer site circuit breakers. Ensure that the voltage across the DC power
source cable leads is 0 V and that there is no chance that the cable leads might become active during
installation.
2. Ground the DC power supply (see
a. Remove the nut and washer from the grounding point on the power supply.
b. Secure each grounding cable lug to the grounding point with the washer and nut.
17