background image

Quick Start Guide

EX9214

IN THIS GUIDE

Step 1: Begin | 1

Step 2: Up and Running | 9

Step 3: Keep Going | 12

Step 1: Begin

IN THIS SECTION

Install the Large Mounting Shelf in an Open-Frame Rack | 3

Mount the EX9214 | 4

Connect Power to the EX9214 | 5

To install and perform initial configuration of a Juniper Networks EX9214 Ethernet Switch, you need:

One large mounting shelf (provided)

Mounting screws. The following mounting screws are provided:

Eight 12-24, ½-in. screws to mount the large mounting shelf on the rack

Sixteen 10-32, ½-in. screws to mount the switch on the rack

Two ¼-20, ½-in. screws to attach the grounding cable lug to the switch

Phillips (+) screwdrivers, numbers 1 and 2 (not provided)

7/16-in. (11-mm) torque-controlled driver or socket wrench (not provided)

One mechanical lift (not provided)

Содержание EX9214

Страница 1: ...Juniper Networks EX9214 Ethernet Switch you need One large mounting shelf provided Mounting screws The following mounting screws are provided Eight 12 24 in screws to mount the large mounting shelf on...

Страница 2: ...st strap with cable provided 2 5 mm flat blade screwdriver not provided Power cord with a plug appropriate for your geographical location for each power supply not provided Ethernet cable with an RJ 4...

Страница 3: ...lves is at 0 04 in 0 02 U above a U division Large Shelf Distance Above U Divisions Holes X 17 26 in 43 8 cm 9 86 U 30 X 15 51 in 39 4 cm 8 86 U 27 X 13 76 in 34 9 cm 7 86 U 24 X 12 01 in 30 5 cm 6 86...

Страница 4: ...rack mount the heaviest unit at the bottom and mount the other units from the bottom to the top in order of decreasing weight To install the switch using a mechanical lift 1 Safely remove all componen...

Страница 5: ...t mounting flanges of the switch align with the holes in the rack rails 9 Move the lift away from the rack 10 Install a 10 32 in screw into each of the open mounting holes aligned with the rack starti...

Страница 6: ...recommended receptacle when using the power supply in one feed mode If you are using the power supply in two feed mode plug the second power cord into the receptacle on the power supply NOTE Each powe...

Страница 7: ...switch 3 Move the input mode switch to position 0 for one feed or position 1 for two feeds NOTE For a fully redundant configuration in two feed mode eight feeds are required For a nonredundant config...

Страница 8: ...wo feeds On INPUT 0 attach the negative DC source power cable lug to the 48V input terminal Repeat this step for INPUT 1 if using two feeds CAUTION Ensure that each power cable lug seats flush against...

Страница 9: ...steadily The INPUT OK is lit amber if the voltage at that input is in reverse polarity Check the polarity of the power cables to fix the condition 13 Set the power switch of the DC power supply to the...

Страница 10: ...crypted password or an SSH public key string DSA or RSA instead of a clear text password 4 Create a management console user account edit root set system login user name authentication plain text passw...

Страница 11: ...t edit root set routing options static route remote subnet next hop destination IP retain no readvertise 11 Configure the telnet service at the edit system services hierarchy level edit root set syste...

Страница 12: ...authorized service personnel Before installing the switch read the planning instructions in the EX Series documentation to ensure that the site meets power environmental and clearance requirements fo...

Страница 13: ...lines remove jewelry including rings necklaces and watches Metal objects heat up when connected to power and ground and can cause serious burns or become welded to the terminals Power Cable Warning J...

Отзывы: