Art. No. SC 1000 KNX
the keyboard.
i
The value transmitted via the communication object of the channel can vary from the preset
value via the keyboard because a gain factor and value offset can be configured optionally
(see "Objects" below).
i
The ETS parameter "Number of integer digits" influences the values entered via the
keyboard. The parameter specifies how many numbers can be preset before the decimal
point via the keyboard and thus defines the value range that can be preset in this way.
i
It is only possible to specify a value via the keyboard in selection operation on the room or
function pages.
Objects
A channel of the function "2-byte value transmitter" has up to 2 KNX communication objects...
-
"D.Output channel x - value transmitter 2-byte" (2-byte transmitting):
Value telegrams are transmitted to the bus via this object after pressing the sensor
element. This can cause, for example, a temperature object, brightness value object or an
object with similar functionality in compliance with KNX DPT 9.0xx to be activated.
This object is not visible when the KNX channel only works as a display function.
-
"D.Input channel x 2-byte value transmitter feedb." (2-byte receiving):
Through this object the device can receive a value feedback that an activated actuator
transmits, for example. The status value, status icon and bar graph for the value
visualization are influenced as a result. Consequently, the feedback object must always be
configured properly so that the status indications of the channel element work correctly.
The feedback of the value must be transmitted by the "actively transmitting" actuator.
If the activated bus device does not have a feedback function, the object "D.Input channel x
- 2-byte value transmitter feedb." can be linked to the object "D.output channel x - 2-byte
value transmitter" via an identical group address.
i
The status elements of the channel are influenced by the object "D.Input channel x 2-byte
value transmitter feedb." . In addition, a value recall by sensor operation or by entry via
keyboard also influences the status elements. During a value recall, the status elements
are updated according to the recalled value regardless of the current feedback value. The
display elements first react again to the feedback object value after a value recall by
operation. As a result, this may cause a leap in value in the status indication when returned