Information for qualified electricians 

5.  Installation and electrical connection 

DANGER 

 

Electric shock in case of accidental contact with live parts. Electric 
shocks may be fatal. Before working on the device, disconnect the 
mains voltage and cover up live parts in the surroundings. 

 

5.1.  Installation of the device 

Observe the admissible temperature range. Ensure sufficient cooling. 

ƒ

  Snap the device onto a DIN EN 60715 mounting rail. The 

connecting terminals must be at the top. 

5.2.   Connection of the device 

Observe the admissible loads. 

L

  Do not connect three-phase AC motors to the actuator. 

L

  On delivery, the switching state is undefined. 

ƒ

  Set the relays to the 

OFF 

position. 

ƒ

  Connect as shown in the example (Fig. 2). 

Fig. 2

 

ƒ

  Connect the bus with the bus terminal (Fig. 1, 3). 

L

  The connection to different phase conductors is possible. 

L

  For current detection, the device is equipped with contactless current 

sensors. Magnetic fields in the immediate vicinity can result in false 
current measurement results. If possible, lay feed and return line 
closely side by side. Do not install devices producing magnetic fields in 
the immediate vicinity of the actuator, e. g. doorbell transformer, power 
contactor, etc. 

 

Содержание KNX 230 .16 REGHM Series

Страница 1: ...e disconnection of the mains supply Do not connect mains voltage consumers together with SELV PELV consumers to the same switching actuator Do not connect three phase AC motors to the actuator The cur...

Страница 2: ...nel and 8 channel switching actuators for C loads Switching of capacitive loads with resulting higher inrush currents 3 1 Product features Bus independent manual switching of relays Operation as n c o...

Страница 3: ...mming button and LED 3 KNX terminal 4 relay output terminals Slide switching position indicator 1 into the ON position The relay contact is closed and the consumer is activated Slide switching positio...

Страница 4: ...onnecting terminals must be at the top 5 2 Connection of the device Observe the admissible loads L Do not connect three phase AC motors to the actuator L On delivery the switching state is undefined S...

Страница 5: ...onnecting terminal slide on the protective cap Lead out the bus line at the rear of the device Slide the cap over the bus terminal Fig 3 A until it is heard to engage 5 4 Removing the cap Press the si...

Страница 6: ...C 45 C Storage temperature 25 C 70 C Total dissipated power 4 channel switching actuators max 4 W 8 channel switching actuators max 8 W Mounting width 4 channel switching actuators 72 mm 4 modules 8...

Страница 7: ...KNX 4 8 channel switching actuator 16A 4 8 channel switching actuator 16 A C load Art Nr 230x 16 REGHM 230x 16REGCHM 8 Switching capacitiy 7...

Страница 8: ...d rectified 11 Guarantee Our products are under guarantee within the scope of the statutory provisions Please return the unit postage paid to our central service department giving a brief description...

Отзывы: