background image

 

KNX 

4-channel analog input module 

 

Ref.-no.: 2214 REG AM 

 

Operating Instructions 
4-channel analog input module 

 

1. Safety 

instructions 

Attention: 
Electrical equipment must be installed and fitted by qualified  
electricians only and in strict observance of the relevant  
accident prevention regulations. 

Failure to observe any of the installation instructions may result in 
fire and other hazards. 

U

s

 

and GND must not be interconnected with the corresponding  

terminals of another device. 
Connected sensors must not be supplied with power from the 
connected KNX/EIB device (Risk of irreparable damage!). 

2. Function 

  This analog input module extends a KNX/EIB weather station  

Art. no. 2224 REG W or a KNX/EIB analog input Art. no. 2114 REG 
A by four additional sensor inputs for analog transducers. 

  Measuring data evaluation and limit processing take place in the  

KNX/EIB device. 

  The analog input module accepts both voltage and current signals: 

Voltage signals:  

0 ... 1 V DC  

 

0 ... 10 V DC 

Current signals:  

0 ... 20 mA DC   

4 ... 20 mA DC 

  The current inputs 4 ... 20 mA can be monitored for wire breakage  

(parameter setting). 

 

Содержание KNX 2214 REG AM

Страница 1: ...rresponding terminals of another device Connected sensors must not be supplied with power from the connected KNX EIB device Risk of irreparable damage 2 Function This analog input module extends a KNX EIB weather station Art no 2224 REG W or a KNX EIB analog input Art no 2114 REG A by four additional sensor inputs for analog transducers Measuring data evaluation and limit processing take place in ...

Страница 2: ...e provided in duplicate and internally interconnected The total current consumption of all sensors supplied this way must not exceed 100 mA In the event of overload or short circuit between US and GND the power will be switched off After removal of the fault the power is switched on again automatically Sensors connected can also be supplied externally e g if their current consumption exceeds 100 m...

Страница 3: ...les without adapting their project configuration and subsequent downloading into the KNX EIB device is not allowed as this will result in system failure 7 Status LED During commissioning of the module On Module ready for operation self test OK Quickly blinking Module initialization in progress Slowly blinking Module not configured in KNX EIB device Off Module initialized and in operation Precondit...

Страница 4: ...C Storage transport temp 25 C 70 C Humidity Ambient storage transport 93 r h max no condensation Protective system IP 20 as per EN 60529 Installation width 4 modules 72 mm Weight approx 150 g Connections Inputs power supply screw terminals single wire 0 5 mm to 4 mm stranded wire without ferrule 0 34 mm to 4 mm stranded wire with ferrule 0 14 mm to 2 5 mm Connection to KNX EIB device 6 pole system...

Страница 5: ...T JUNG GMBH CO KG Service Center Kupferstr 17 19 D 44532 Lünen Service Line 49 0 23 55 80 65 51 Telefax 49 0 23 55 80 61 89 E Mail mail vki jung de Technik allgemein Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 E Mail mail vkm jung de Technik KNX EIB Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 E Mail mail vkm jung de The Sign is a free trade sign addressed exclusiv...

Отзывы: