Jung IPS 100 REG Скачать руководство пользователя страница 4

When additional bus devices are added, the corresponding physical addresses can be 
assigned twice. Delete the additional physical addresses – press the programming button 
(9) for approx. 10 seconds – and assign them again.  

5 Appendix 

5.1 Technical data 

Power over Ethernet supply 
Power over Ethernet 

IEEE802.3af 

Rated voltage 

DC 48 V 

Power consumption 

max. 0.8 W 

External supply 
Rated voltage 

AC 12 ... 24 V SELV 

Rated voltage 

DC 12 ... 30 V SELV 

Power consumption 

max. 1.7 W 

Connection of power supply 

Connection terminal 

Ambient conditions 
Ambient temperature 

-5 ... +45 °C 

Storage/transport temperature 

-25 ... +70 °C 

Relative humidity 

5 ... 93 % (No moisture condensation) 

Fitting width 

36 mm / 2 modules 

Weight 

approx. 100 g 

Network communication 
IP communication 

Ethernet 10BaseT 

IP transmission rate 

10 Mbit/s 

IP connection mode 

RJ45 socket 

Protocols 

ARP, ICMP, IGMP, UDP/IP, DHCP 

KNXnet/IP 

Core, Tunneling, Device Management 

KNX 
KNX medium 

TP 1 

Commissioning mode 

S mode 

Rated voltage KNX 

DC 21 V ... 32 V SELV 

Connection mode KNX 

Connection terminal 

Current consumption KNX 

max. 10 mA 

5.2 Troubleshooting 

After installation of the ETS3 driver and enabling of the device as a communication 
interface, an error message that the class is not known appears on the PC. 

Microsoft

®

.Net Framework not installed. 

Download and install Microsoft

®

.Net Framework from the Microsoft website. 

5.3 Accessories 

Power supply AC 24V~

Art.-No.: WSSV10

4/5 

82571223 
J:0082571223 

06.04.2010 

KNX IP interface 

Отзывы: