Jung FMDW360WW Скачать руководство пользователя страница 1

eNet motion detector

eNet motion detector
Art. no.: FMDW360WW

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

The radio communication takes place via a non-exclusively available transmission path, and is
therefore not suitable for safety-related applications, such as emergency stop and emergency
call.

These instructions are an integral part of the product, and must remain with the end customer.

2

Battery safety instructions

This device or its accessories are supplied with batteries in the form of alkaline batteries LR03.

DANGER! Batteries can be swallowed. This can lead directly to death by suffocation.
Keep new and used batteries away from children.
Do not use devices if the battery compartment does not close securely and keep away from
children.
If you suspect that a battery has been swallowed or is in any orifice of the body, seek immediate
medical attention.

WARNING! Improper handling of batteries can result in explosion, fire or chemical burn due to
leakage.

Do not heat or throw batteries into fire.
Do not reverse polarity, short-circuit or recharge batteries.
Do not deform or disassemble batteries.
Replace batteries only with an identical or equivalent type.
Remove empty batteries immediately and dispose of in an environmentally friendly manner.
Exchange all batteries at the same time. Only use batteries of the same type and manufacturer.
Do not combine old and new batteries.

3

Intended use

Automatic switching of lighting depending on the heat motion and ambient brightness

Operation only with radio actuators for switching and dimming from the eNet system

Ceiling mounting, surface-mounted, in dry interiors

4

 Function

Product characteristics

LED for signalling

Battery-powered device

Brightness threshold settable

Run-on time adjustable

Sensitivity can be set

Can be set with eNet server:

Disabling of manual commissioning

Longer run-on time adjustable

Brightness threshold settable

Power saving level

1 / 12

82598403

25.07.2019

J0082598403

Содержание FMDW360WW

Страница 1: ...allowed or is in any orifice of the body seek immediate medical attention WARNING Improper handling of batteries can result in explosion fire or chemical burn due to leakage Do not heat or throw batteries into fire Do not reverse polarity short circuit or recharge batteries Do not deform or disassemble batteries Replace batteries only with an identical or equivalent type Remove empty batteries imm...

Страница 2: ...r Inserting batteries 5 Operation For manual operation a radio hand transmitter for example must be connected to the radio ac tuator in addition to the ceiling detector The parameter Manual switch off of run on time is switched off in the actuator factory setting The radio transmitter can be used to make the following settings The actuator can be switched on independently of the brightness for the...

Страница 3: ...gure 1 Detection field 1 Range for tangential movement on the ground is approx Ø 8 m Figure 1 2 Range for radial movement on the ground is approx Ø 5 m Figure 1 These specifications refer to mounting on the ceiling at a mounting height of 2 5 m The detec tion field becomes larger for mounting heights above 2 5 m while the detection density and sensitivity are reduced at the same time Select a vibr...

Страница 4: ...other Sensitivity brightness threshold and run on time are set for each device When motion is detected each motion detector sends a telegram to the ac tuator The actuator evaluates the telegrams of the individual motion detectors and switches the load accordingly The longest run on time sent is always executed 7 Commissioning DANGER Mortal danger of electric shock During commissioning cover the pa...

Страница 5: ...usters are set to PC Values for the run on time and the brightness threshold are preset at the factory As soon as one of the two adjusters is shifted from position PC and a telegram is sub sequently triggered the sensor operates with the currently set values Adjuster Position Value Sens 5 max 100 Time 6 PC 2 min Lux 7 PC 2000 lx Insert batteries Obey the battery safety instructions If the sensor i...

Страница 6: ...on command of a transmitter e g of a wall transmitter that does not transmit its own run on time The run on time saved in an actuator can only be subsequently changed with the eNet Server or after a factory reset of the actuator Turn adjuster Time 6 Figure 4 to the desired value Setting the brightness threshold The brightness value measured at the sensor corresponds to the brightness below the ins...

Страница 7: ...sful All memory locations in the actuator or sensor are occupied Press the Prog button once again for longer than 4 seconds to terminate the program ming mode prematurely Disconnecting connection to an actuator Carry out the same steps as when connecting see the chapter Connecting to radio actu ator The status LED of the actuator flashes quickly for 5 seconds The actuator is disconnec ted from the...

Страница 8: ...ut push on cover Ø approx 8 0 m Pull off push on cover Using scissors cut out push on cover along the marked lines as required Push on push on cover The detection field can alternatively be limited by reducing the sensitivity 8 Disposal of batteries Remove empty batteries immediately and dispose of in an environmentally friendly manner Do not throw batteries into household waste Consult your local...

Страница 9: ...g Explanations Function Motion detection not used Default setting Motion detec tion Motion detection The channel works as a mo tion detector Unused The channel is not displayed in the eNet SMART HOME app and is disabled for use in the commissioning interface Advanced device settings Parameter name Setting options Basic setting Explanations Manual commissioning On Off Basic setting On Disables manu...

Страница 10: ...channel settings Parameter name Setting options Basic setting Explanations Manual commissioning On Off Basic setting On Blocks manual commissioning for the device channel In the Off setting the device can not be reset to the factory set ting Local Operation On Off Basic setting On Blocks the device channel for local operation With this device the parameter has no function Power saving level Low Me...

Страница 11: ... Send brightness values auto matically The device sends the meas ured brightness values Der eNet Server can use these to e g control brightness de pendent functions 11 Troubleshooting Actuator does not switch on Cause 1 The ambient brightness is greater than the brightness threshold set on the sensor Set brightness threshold Cause 2 Sensor does not detect any motion Increase sensitivity Check the ...

Страница 12: ...tection field sensor detects motion constantly Remove interference sources if possible Reduce sensitivity Limit the detection field using the push on cover 12 Conformity Albrecht Jung GmbH Co KG hereby declares that the radio system type art no FMD W360WW meets the directive 2014 53 EU You can find the full article number on the device The complete text of the EU Declaration of Conformity is avail...

Отзывы: