LB management
eNet radio centre plate
Parameters
Setting options, Basic
setting
Explanations
Minimum switch-
ing repeat time
100 ms ... 10 sec
Basic setting: 100 ms
Limits the switching speed of the device by in-
creasing the value, in order to protect the load,
for example. Only when the set time has elapsed
is switching possible again. The last command
during the blocking time is executed after a delay.
The switching repeat time starts after each
switching operation.
Channel settings "2-wire switching"
Parameters
Setting options, Basic
setting
Explanations
Switch-on delay
0 s … 24 h
Basic setting: 0 s
The load switches on after a delay. Repeated
switch-on commands restart the delay time. If the
load has not yet been switched on due to the
delay when a switch-off command comes, then
the load will remain off.
Switch-off delay
0 s … 24 h
Basic setting: 0 s
The load switches off after a delay. Repeated
switch-off commands restart the delay time. If the
load has not yet been switched off due to the
delay when a switch-on command comes, then
the load will remain on.
Run-on time
0 s … 24 h
Basic setting: 0 s
If a run-on time is entered and the "Use run-on
time" parameter is activated, the actuator no
longer remains permanently switched on, but
only for the duration of the run-on time entered
here or transmitted by a motion detector. The
run-on time is restarted if actuation is repeated.
A motion detector command without transmitted
run-on time (e.g. from an extension) leads to
switching on for the duration of the run-on time
entered here. If no run-on time is entered here,
the default run-on time of 2 minutes is applied.
Use run-on time
On, Off
Basic setting: Off
On:
If a run-on time is configured (≠ 0 s), in addition
to motion detector commands, all switching or
dimming commands also lead to switching on for
the duration of the run-on time.
If no run-on time is configured (= 0 s), all switch-
ing or dimming commands result in permanent
switching of the load.
As soon as the attachment receives a motion de-
tector command, the transmitted run-on time is
automatically entered in the "Run-on time" para-
meter and this then also applies to all switching
and dimming commands.
Off:
Only motion detector commands lead to switch-
ing on for the duration of the transmitted or set
run-on time. The load is permanently switched for
switching and dimming commands.