Presence detector mini
Detection angle
360°
Range
Ø approx. 12 m (installation height 3 m)
Brightness sensor
Measuring range
10 ... 2000 lx
Accuracy > 80 lx
± 5%
Accuracy ≤ 80 lx
± 10 lx
Only for "Universal" version:
Temperature sensor
Measuring range
approx. -20 ... +55 °C
Accuracy
± 1 K
IR remote control
Battery type
1×Lithium CR 2450N
9
Troubleshooting
Light does not switch on despite motion detection and low lighting
Cause 1: Wrong function block active.
Change function block switch-over.
Cause 2: Brightness threshold set is too low.
Increase the brightness threshold with the remote control or parameter setting.
Light switches on despite sufficient ambient lighting
Cause 1: Signal function is active and the device therefore operates independently of the bright-
ness.
Check programming.
Cause 2: Device operates independently of the brightness.
Adjust the brightness threshold with the remote control.
Adjust parameter setting for brightness threshold.
Light switches off briefly and then on again immediately
Cause 1: Luminaires in the detection field.
Set the configuration barrier parameter so that cooling light bulbs are not detected.
Cause 2: The brightness threshold set is not reached after switching off. Device switches on
again immediately during motion detection.
Increase brightness threshold.
Light switches off early despite motion detection and low lighting
Cause 1: The set time is too short.
Increase the time with the remote control or parameter setting.
Cause 2: Detection problem, the surface to be monitored is not in the detection field, or furniture
or pillars are in the way.
Check detection field, extend presence detector extension if necessary.
Device responds even without any motion in the detection field
Cause: Interference sources in the detection field or device settings are too sensitive.
Limit detection field, remove interference sources.
Adjust sensitivity by one level with blue sensitivity switch (7) or with remote control.
Reduce sensitivity in parameter setting.
The sensitivity should be reduced by 1 to 2 levels in small spaces.
12 / 13
82589823
25.02.2020
j0082589823