 Function

System information

This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.

The function of this device depends upon the software. Detailed information on loadable soft-
ware and attainable functionality as well as the software itself can be obtained from the manu-
facturer´s product database.

The device can be updated. Firmware can be easily updated with the Jung ETS Service App
(additional software).

The device is KNX Data Secure capable. KNX Data Secure offers protection against manipula-
tion in building automation and can be configured in the ETS project. Detailed specialist know-
ledge is required. A device certificate, which is attached to the device, is required for safe com-
missioning. During mounting, the certificate must be removed from the device and stored se-
curely.

Planning, installation and commissioning of the device are carried out with the aid of the ETS,
version 5.7.3 and above.

Intended use

Switching of electrical loads with potential-free contacts

Switching of electrically-driven Venetian blinds, roller shutters, awnings and similar
hangings

Mounting on DIN rail according to EN 60715 in small distribution boards

Product characteristics

Outputs can be operated manually, construction site mode

Feedback in manual mode and in bus mode

Disabling of individual outputs manually or by bus

Status feedback (e. g. wind alarm)

KNX Data Secure compatible

Updateable with Jung ETS Service App

Characteristics switch operation

Operation as NO or NC contacts

Feedback function

Logic and restraint function

Central switching functions with collective feedback

Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time

Scene function

Operating hours counter

Characteristics blinds operation

Suitable for AC motors 110...230 V

Operating modes "Venetian blind with slats", "Roller shutter/awning", "Venting louver/roof
window"

Blind/shutter position directly controllable

Slat position directly controllable

Feedback of movement status, blind/shutter position and slat position

Forced position through higher-level controller

Safety function: 3 independent wind alarms, rain alarm, frost alarm

Sun protection function with heating/cooling operation

Disabling function (lock-out protection)

Scene function

2 / 9

82402603

15.05.2020

J0082402603

Содержание 230061SR

Страница 1: ... Do not connect loads for mains voltage and SELV PELV together to the device For parallel connection of several motors to an output it is essential to observe the correspond ing instructions of the manufacturers and to use a cut off relay if necessary The motors may be destroyed Use only venetian blind motors with mechanical or electronic limit switches Check the limit switches for correct adjustm...

Страница 2: ...otential free contacts Switching of electrically driven Venetian blinds roller shutters awnings and similar hangings Mounting on DIN rail according to EN 60715 in small distribution boards Product characteristics Outputs can be operated manually construction site mode Feedback in manual mode and in bus mode Disabling of individual outputs manually or by bus Status feedback e g wind alarm KNX Data ...

Страница 3: ...h off adjust slats or stop Long Move hanging downwards 11 LED Dž ON relay outputs open manual control active 12 Button ALL OFF Open all relay outputs stop drives In operation with the button field the device distinguishes between a short and a long press Short actuation for less than 1 s Long actuation of between 1 and 5 s In switching operation the device distinguishes between the operating modes ...

Страница 4: ...manual operation is switched off Switching outputs depending on the programming the output relays switch to the position that is active after the manual mode is switched off e g to the forced position logic func tion Blind shutter outputs depending on the programming the hangings move to the position that is active after the manual mode is switched off e g to the forced position safety or sun prot...

Страница 5: ... Press button ǃ 6 repeatedly until LED A1 4 of the desired output or output pair flashes Press the DŽ 9 and Dž 10 buttons simultaneously for approx 5 s Selected output is disabled The status LED A1 4 of the selected output or output pair flashes quickly A disabled output can be operated in manual mode Re enabling outputs The device is in continuous manual mode One or more outputs were disabled in ma...

Страница 6: ... voltages For switched loads configure the outputs as a switching output For Venetian blind operation configure the outputs as a Venetian blind output Two adja cent relay outputs form a Venetian blind output Delivery state The outputs can be manually operated Outputs are set as venetion blind outputs The total current capacity of neighbouring outputs is a maximum of 20 A Figure 4 Total current cap...

Страница 7: ...ut ETS programming Master reset The master reset restores the basic device setting physical address 15 15 255 firmware re mains in place The device must then be recommissioned with the ETS Manual operation is possible During secure operation A master reset deactivates device security The device can then be re commissioned with the device certificate Performing a master reset Precondition The safe ...

Страница 8: ...ormer 1200 VA Fluorescent lamps T5 T8 uncompensated 1000 W parallel compensated 1160 W 140 μF twin lamp circuit 2300 W 140 μF Compact fluorescent lamps uncompensated 1000 W parallel compensated 1160 W 140 μF Mercury vapour lamps uncompensated 1000 W parallel compensated 1160 W 140 μF Fitting width Art no 230061SR 72 mm 4 module Art no 230161SR 144 mm 8 module Art no 230241SR 216 mm 12 module Weigh...

Страница 9: ...s provided in accordance with statutory requirements via the specialist trade ALBRECHT JUNG GMBH CO KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 9 9 82402603 15 05 2020 J0082402603 ...