background image

 

KNX/EIB 

Product documentation

 

Page: 1 of 29 

 

Hardware description

 

2-gang  
standard push button sensor 'TSM' 

 

Sensor

 

Product name

 

2-gang standard push button sensor 'TSM' 

Design:

 

flush-mounted (UP) 

Article no.

 

2072 TSM 

ETS search path

 

Push button / Push button 2-gang / 2-gang standard push button sensor 'TSM' 

Issue:

 

21.09.2005 

Functional description:

 

 

The 2-gang standard push button sensor 'TSM' is plugged onto a flush-mounted bus coupling unit (BCU) (cf. 
connection diagram). After a press on the key, the push button sensor will transmit software-dependent telegrams 
to the KNX / EIB. These may be telegrams for switching, pushbutton operation, dimming or for shutter control. It is 
also possible to program value-transmitting functions such as dimming value transmitter or light-scene extension 
units. A blue operation LED can serve as orientation lighting 

 

Layout:

 

Dimensions: Controls: 

 

A

B

C

1

3

2

4

 

 

 
Width:  70 mm (without 

frame) 

 

Height:  70 mm (without 

frame) 

 

Depth:  7 mm (without PEI) 

 
A: 2 rockers (keys 1 to 4: key-press 

on upper and lower half of 
respective rocker) 

 

The device is operated with the 
corresponding push button 
sensor module covers. The 
covers must be ordered 
separately: 
2 x FD..902 TSA.. 

 

Covers with article nos. 
FD..90x TSA NA.. can be 
labelled. For labelling, 
commercial-grade foils can be 
printed with the JUNG inscription 
software and inserted into the 
keys. 

 
B: 2 status LEDs (red), one per 

rocker 

 
C: 1 operation LED (blue) 
 
 

Technical Data

 

Type of protection:

 

IP 20 

Safety class: 

III 

Mark of approval:

 

KNX / EIB 

Ambient temperature:

 

-5 °C ... +45 °C 

Storage / transport temperature:

 

-25 °C ... +70 °C (storage above +45 °C reduces the lifetime) 

Mounting position: 

any 

Minimum distances:

 

none 

Type of fastening:

 

plugging onto flush-mounted (BCU 1) 

KNX / EIB supply

 

 

Voltage:

 

21 – 32 V DC (SELV) via flush-mounted BCU 

Power consumption:

 

typically 150 mW 

Connection:

 

2 x 5-pole pin contact strip 

External supply 

--- 

Содержание 2072 TSM

Страница 1: ...tation lighting Layout Dimensions Controls A B C 1 3 2 4 Width 70 mm without frame Height 70 mm without frame Depth 7 mm without PEI A 2 rockers keys 1 to 4 key press on upper and lower half of respec...

Страница 2: ...erconnected via user interface B Fasten the 2 gang standard push button sensor TSM with the plastic screws E supplied with the device to the KNX EIB bus coupling unit The screws serve as a protection...

Страница 3: ...atus Switching status 100312 1 2 2 Switching acknowledgement Switching acknowledgement 100A12 1 2 3 Dimming Dimming 102A01 0 1 4 Shutter Shutter 102B01 0 1 5 Shutter with status object Shutter with st...

Страница 4: ...of assignments max 10 maximum length of table 20 Communication objects 2 Object Function Name Type Flag 0 Switching Rocker 1 1 bit C W T 1 Switching Rocker 2 1 bit C W T Object description Objects 0...

Страница 5: ...OFF ON Defines the command transmitted on pressing of key 2 4 Rocker 1 Function status LED OFF ON Determines the status of the operation LED Rocker 2 Function status LED OFF ON Defines the status of t...

Страница 6: ...mber of assignments max 9 maximum length of table 17 Communication objects 2 Object Function Name Type Flag 0 Switching Rocker 1 1 bit C W T 1 Switching Rocker 2 1 bit C W T Object description Objects...

Страница 7: ...N Defines the command transmitted on pressing of key 1 3 Command on pressing of keys 2 4 OFF ON Defines the command transmitted on pressing of key 2 4 Rocker 1 Function status LED OFF ON Defines the s...

Страница 8: ...ommunication objects 4 Object Function Name Type Flag 0 Switching Rocker 1 1 bit C W T 1 Switching Rocker 2 1 bit C W T 2 Dimming Rocker 1 4 bit C T 3 Dimming Rocker 2 4 bit C T Object description Obj...

Страница 9: ...ration LED Function status LED OFF ON Defines the status of the status LED Software remarks The status LED indicates the current status of the switching object If a key is pressed e g ON and if the pu...

Страница 10: ...operation Rocker 1 1 bit C W T 1 Short time operation Rocker 2 1 bit C W T 2 Long time operation Rocker 1 1 bit C W T 3 Long time operation Rocker 2 1 bit C W T Object description Objects 0 1 Short ti...

Страница 11: ...n LED status indicator 6 Status Operation LED 1 bit C W Object description Objects 0 1 Short time operation 1 bit object for short time operation of a shutter 2 3 Long time operation 1 bit object for...

Страница 12: ...130 ms 2 1 s 33s Defines the time base up to long time operation Time base factor Depending on parameter Operating concept Time between short and long time operation factor 2 255 3 255 30 Defines the...

Страница 13: ...thus the evaluation of the keys The rocker 1 function is assigned to the two keys 1 and 2 on the left The function is activated in this case by a press on the upper and lower part of the the lefthand...

Страница 14: ...T1 T2 Releasing STEP no action STEP MOVE key pressed Operating concept Move Step A press on the key triggers a Move telegram Slat adjustment time T2 is started Releasing the key before the slat adjust...

Страница 15: ...will cause a Step telegram to be transmitted Only if the key is kept pressed after time T1 has elapsed will the push button sensor trigger a Move telegram Slat adjustment time T2 is started If the key...

Страница 16: ...hange of relative brightness between 0 and 100 2 Short time operation 1 bit object for short time operation of a shutter 3 Long time operation 1 bit object for long time operation of a shutter Scope o...

Страница 17: ...hich the status LED is on when a key is pressed Only if Status LED function key press indicator Key function 1 3 brighter ON 2 4 darker OFF 1 3 darker OFF 2 4 brighter ON Defines the command transmitt...

Страница 18: ...Time between two telegrams base 0 5 ms 8 ms 130 ms 2 1 s 33 s Defines the time base between two telegrams Time between STEP STEP or between STEP MOVE Time base factor Time between two telegrams facto...

Страница 19: ...r 4 bit C T Object description Objects 0 2 Switching 1 bit object for the transmission of switching telegrams ON OFF 3 Dimming 4 bit object for change of relative brightness between 0 and 100 Scope of...

Страница 20: ...me 0 5 s 1 s 2 1 s 4 2 s 8 4 s Defines the time during which the status LED is on when a key is pressed Only if Status LED function key press indicator Command on pressing of key 1 3 press ON release...

Страница 21: ...nes the time base for a key press to send a telegram Time base factor Time between switching and dimming factor 2 127 2 127 3 Defines the time factor for a key press to send a dimming telegram Time ba...

Страница 22: ...cription Objects 0 1 Switching 1 bit object for the transmission of switching telegrams ON OFF 2 Short time operation 1 bit object for short time operation of a shutter 3 Long time operation 1 bit obj...

Страница 23: ...5 s 2 25 s 3 s 4 5 s 6 s 10 s 15 s Defines the time during which the status LED is on when a key is pressed Only if Status LED function key press indicator Command on pressing of key 1 3 press ON rele...

Страница 24: ...1 s 33 s Defines the time base between two telegrams Time between STEP STEP or between STEP MOVE Time base factor Time between two telegrams factor 2 255 2 255 46 Defines the time factor between two t...

Страница 25: ...Switching Key 1 1 bit C W T 1 Switching Key 2 1 bit C W T 2 Switching Key 3 1 bit C W T 3 Switching Key 4 1 bit C W T 4 LED control Status LED 1 1 bit C W T 5 LED control Status LED 2 1 bit C W T Obje...

Страница 26: ...g of key 1 press ON release ON press ON release OFF press ON release press OFF release ON press OFF release OFF press OFF release press TOGGLE release press release ON press release OFF press release...

Страница 27: ...ects 1 Object Function Name Type Flag 0 Value light scene Rockers 1 byte C T Object description Objects 0 Value light scene 1 byte object for transmitting value telegrams of for recalling light scenes...

Страница 28: ...5 3 Defines the value transmitted when key 2 is pressed Rocker 1 with Mode of operation light scene recall with without storage function Light scene 1 8 Key 1 1 8 1 Defines the value transmitted when...

Страница 29: ...function for more than 5 s a storage telegram corresponding to the parameterized light scene will be transmitted and the status LED is lit up for 4 s Pressing a key with storage function for a time be...

Отзывы: