background image

LB management

Power DALI rotary controller TW, DALI rotary controller TW

Power DALI rotary controller TW
Art. no.: 1741DSTE
DALI rotary controller TW
Art. no.: 1740DSTE

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.

These instructions are an integral part of the product, and must remain with the end customer.

2

Device components

Figure 1

(1)

DALI rotary control device TW

(2)

Frame

(3)

Central plate

(4)

Control knob

(5)

Screw terminals

3

Function

Intended use

Brightness setting for luminaires with DALI interface

Setting the colour temperature for luminaires with DALI Device Type 8 for Tunable White
in accordance with IEC 62386-209

Mounting in appliance box according to DIN 49073

Product characteristics

The Power DALI rotary controller TW supplies the control current for up to 28 DALI sub-
scribers.

The DALI rotary controller TW takes power from the DALI voltage, which must be supplied
by an external DALI power supply in accordance with IEC 62386-101.

1 / 5

82594753

14.09.2021

J0082594753

Содержание 1741DSTE

Страница 1: ...or load These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 1 DALI rotary control device TW 2 Frame 3 Central plate 4 Control knob 5 Screw terminals 3 Function Intended use Brightness setting for luminaires with DALI interface Setting the colour temperature for luminaires with DALI Device Type 8 for Tunable White in accordance w...

Страница 2: ...ontrol knob Turn left W warmer light reduce colour temperature Turn right C colder light increase colour temperature Save switch on brightness If the lighting is not always to be switched on with the same brightness then this can be saved as a switch on brightness Switch on light Set required switch on brightness Press the control knob briefly twice in succession double click The lighting briefly ...

Страница 3: ...orresponding cir cuit breakers Cover up live parts 5 1 Fitting and electrical connection Connecting and fitting the device Figure 3 Power DALI rotary control device TW wiring plan Figure 4 DALI rotary control device TW wiring plan 1 Power DALI rotary control device TW 6 DALI subscriber e g DALI EVG DALI Device Type 8 for Turnable White 7 DALI rotary control device TW 8 DALI power supply 3 5 825947...

Страница 4: ... increase Press the control knob for longer than 10 seconds The lighting switches briefly off and on again The basic brightness is saved Saving colour temperature limiting values The setting range of the DALI rotary control device can be adjusted to the colour temperature of the luminaire using this setting When saving the colour temperature you must ensure that the last turn of the pressed contro...

Страница 5: ...tion max 2 mA Ambient temperature 5 45 C Colour temperature setting 2000 10000 K 6 2 Troubleshooting The colour temperature cannot be changed Cause 1 Before saving the temperature limiting values the control knob was turned in the wrong direction Delete basic brightness and colour temperature limiting values Then repeat the save pro cedure Cause 2 The activated luminaire does not include a DALI De...