10 Technical data
94
V1.00/EN/00709725 [Thyristor power controller TYA S202]
10.3.1Display and measuring accuracy
All specifications refer to the power controller nominal data.
10.4 Binary output (fault signal output master only)
10.5 General specifications
Current
0 (4) to 20 mA R
i
= 50
Ω
Voltage
0 (2) to 10 V R
i
= 25 k
Ω
0 (1) to 5 V R
i
= 25 k
Ω
Mains voltage: ±2.5 %
Load current: ±1 %
Load voltage:
±1 %
Analog input
Voltage/current: ±1 %
Relay (changeover contact)
without contact protection
circuit
30,000 switching operations at a switching capacity of AC 230 V / 3 A
(1.5 A), 50 Hz, B300 (UL 508)
Thyristor control:
Setpoint specification
current input
(can carry current up to 25 mA)
Setpoint specification
voltage input
(surge proof up to max. DC 32 V)
Via interface
Continuous
The power controller provides the power for the load continuously depending on the configured
setpoint specification.
Possible
Logic
(Solid state relay SSR)
The power controller acts like a switch and switches the load ON and OFF. The switching thresh-
old is always in the middle of the configured current/voltage range
At 4 to 20 mA, it is 12 mA; at 0 to 10 V, it is 5 V.
Possible
Circuit variants
- Three-phase economy circuit in master slave operation
Operating modes
- Burst-firing operation for resistive or transformer load
Load types
All resistive loads through to inductive loads are permitted.
In the case of transformer loads, the nominal induction of 1.2 tesla must not
be exceeded (value is 1.45 T in the case of mains overvoltage).
Special features
- Dual energy management
- Soft start with pulse groups
Electrical connection
For type 709066/X -0X-020...
Control and load leads are connected via screw terminals.
From type 709066/X -0X-032...
Control cables are connected via screw terminals and load leads via cable
lugs DIN 46235 and DIN 46234 or tubular cable lugs.
Operating conditions
The power controller is designed as a built-in device according to:
EN 50178,
pollution degree 2, overvoltage category Ü III
Содержание TYA S202
Страница 8: ...8 V1 00 EN 00709725 Thyristor power controller TYA S202 contents...
Страница 16: ...1 Introduction 16 V1 00 EN 00709725 Thyristor power controller TYA S202 Conformity Standard RoHS 2002 95 EC...
Страница 22: ...2 Mounting 22 V1 00 EN 00709725 Thyristor power controller TYA S202 TYA S202 100A TYA 6202 150 200A...
Страница 23: ...V1 00 EN 00709725 Thyristor power controller TYA S202 23 2 Mounting TYA S202 250A...
Страница 26: ...2 Mounting 26 V1 00 EN 00709725 Thyristor power controller TYA S202 2 2 2 Type 709066 X 0X 032 0X XXX XX...
Страница 27: ...V1 00 EN 00709725 Thyristor power controller TYA S202 27 2 Mounting 2 2 3 Type 709066 X 0X 050 0X XXX XX...
Страница 28: ...2 Mounting 28 V1 00 EN 00709725 Thyristor power controller TYA S202 2 2 4 Type 709066 X 0X 100 0X XXX XX...
Страница 52: ...4 Operation 52 V1 00 EN 00709725 Thyristor power controller TYA S202...
Страница 66: ...5 Configuration 66 V1 00 EN 00709725 Thyristor power controller TYA S202...
Страница 92: ...92 V1 00 EN 00709725 Thyristor power controller TYA S202 9 What to do if...
Страница 98: ...10 Technical data 98 V1 00 EN 00709725 Thyristor power controller TYA S202...