9 Startup
32
9.4
Window opening function
The window opening function can be set using three parameters. The principle switching points are de-
fined using the switching point and release point. In addition, hysteresis can also be set for the switching
point and release point. The hysteresis function is deactivated as soon as the hysteresis
parameter >= (Sp - Rsp)/2 is configured.
9.5
Window closing function
The window closing function constitutes the inverted function of the window opening function.
(1)
Release point
(2)
Switching point
(3)
Flow velocity
(4)
Hysteresis
(1)
(2)
(3)
[
cm/s
]
(4)
(4)
0
1
(1)
Release point
(2)
Switching point
(3)
Flow velocity
(4)
Hysteresis
(1)
(2)
(3)
[
cm/s
]
(4)
(4)
0
1
Содержание PINOS L02
Страница 1: ...40604100T90Z000K000 V2 00 DE EN 00691112 JUMO PINOS L02 Betriebsanleitung Operating Manual...
Страница 2: ......
Страница 3: ...40604100T90Z000K000 DE 00691112 JUMO PINOS L02 Kalorimetrischer Str mungssensor Betriebsanleitung...
Страница 4: ......
Страница 18: ...3 Ger teausf hrung identifizieren 16...
Страница 28: ...7 Anzeige und Bedienelemente 26...
Страница 42: ...10 Wartung 40...
Страница 44: ...11 China RoHS 42...
Страница 45: ......
Страница 47: ...40604100T90Z000K000 EN 00691112 JUMO PINOS L02 Calorimetric flow sensor Operating Manual...
Страница 48: ......
Страница 52: ...1 Safety information 6...
Страница 62: ...3 Identifying the device version 16...
Страница 86: ...10 Maintenance 40...
Страница 88: ...11 China RoHS 42...
Страница 89: ......
Страница 91: ......
Страница 92: ......