8 Programming
73
8.4.3 Scaling
The scaling start/end value and the dimen-
sion (unit) are defined to record the meas-
urement. For the alpha-numerical presenta-
tion of the measurement on the display and
on the chart, the number format is selected.
Example:
A temperature transmitter supplies a voltage
within the range of 0 — 10V. This range cor-
responds to a temperature of 200 — 600°C.
Programming:
Unit: °C
Scaling start:
200
Scaling end:
600
Number format:
XXX.X
Section 7.4
Display
Edit
Selection/input
with keys
Enter
Continue with
SCALING
E
3 SCALING
Select recording channel
h
,
R
E
2
2
3 DIMENSION: _ _ _ _
5 digits freely selectable
h
,
R
,
S
E
3
3
3 ZERO
+200.0 °C
Input start of scaling
h
,
R
,
l
,
r
,
S
E
4
4
3 FULL
+600.0 °C
Input end of scaling
h
,
R
,
l
,
r
,
S
E
Check
zero
<>
full
5
5
3 DECIMAL POINT:
x.xxx
Select decimal place :
AUTO, x.xxx, xx.xx, xxx.x,
xxxx.
h
,
R
E
h
forwards
R
backwards
Содержание LOGOLINE 500d
Страница 106: ...9 Consumables 106 9 2 Removing and replacing the chart cassette S F ENTER E S F ENTER E...
Страница 108: ...9 Consumables 108 9 2 1 Changing the roll chart 1 5 2 6 3 7 4 8...
Страница 109: ...9 Consumables 109 9 2 2 Changing the fanfold chart 1 4 2 5 3...
Страница 110: ...110 10 Extra Codes and accessories 10 1 Converting the chart cassette 1 3 2 4...
Страница 113: ...10 Extra Codes and accessories 113 ER 8 Error Power L L L1 N 97 98 99 TxD RxD RxD TxD GND 8 1 8 2 8 3...
Страница 136: ......
Страница 137: ......
Страница 138: ......
Страница 139: ......