10 Troubleshooting
10.3
Error messages outside NAMUR
Error messages outside NAMUR classification NE 107 are displayed by symbols and a two-line mes-
sage (alternating with the process display).
Symbol
Designation
Functional check
Message
Cause
Remedy
Simulation
active
Simulation mode is active.
Deactivate simulation mode. Alterna-
tively: Restart device.
Symbol
Designation
Outside the specification
Message
Cause
Remedy
Outside the
specification
The device is operated outside the de-
vice specifications.
Operate the device within the device
specifications.
Undervoltage
The voltage supply to the device is in-
sufficient.
Check the voltage supply to the device.
Overload at
C/Q or DO
The switching outputs are overloaded. Check the connection and load of the
switching outputs.
Error
analog output
The burden at the analog output is too
high.
Observe the specified values for the
burden of the analog output.
Max. pulse freq.
exceeded
The maximum output frequency of the
pulse output has been exceeded.
Check the configuration of the pulse
output.
Empty conduit
The meter run is empty.
Fill the meter run or the system.
Air bubbles
detected
Air bubbles have been detected in the
system.
Bleed the system.
Symbol
Designation
Caution
Message
Cause
Remedy
Batch error
The maximum batch time has been ex-
ceeded.
Check the filling volume of the batch
and restart the process.
A measurement error occurred during
the batch.
Check the process for measurement
errors and restart the process.