9 Configuration level
57
9.6.5
Error signal
If, for the measured value 1, the value is exceeded, not
reached, or a diagnostic error occurs, the current or voltage
value set on the analog output is output as a so-called error
signal.
For signal type 4 to 20 mA
3.4 or 21.2 mA
For signal type 0 to 20 mA
0 or 21.2 mA
For signal type 2 to 10 V
1.7 or 10.4 V
For signal type 0 to 10 V
0 or 10.4 V
9.6.6
Logic output
This setting only appears if "Logic output" is set under
Chapter 9.6.1.
This sets whether the switching status of the controller (K1)
or switching status of the limit value (K2) is output.
Controller (K1)
Limit value (K2)
Parameters
Comment
Value range
(default setting in bold)